Test Operation
Part 5 Field Settings and Test Operation
189
Caution
Operation with the stop valve closed may result in compressor malfunction.
About test operation
If the system is started about 12 minutes after the indoor and outdoor units are opened or later,
the compressor will not operate and H2P will light up.
Before operating, always check whether the symbols indicated on the LED display are those in
the table under “1. Powering on ~ test operation (2)”.
In order to ensure uniform refrigerant distribution, it may take up to around 10 minutes for the
compressor to start up after the unit starting operation. This is not a malfunction.
The operation check is not for checking individual indoor units. After completing the operation
check, operate the system normally with the remote controller.
Test operation can't be performed when the unit is in other modes such as refrigerant recycling
mode.
Never perform test operation with discharge pipe thermistor (R2T), suction pipe thermistor
(R3T) and pressure sensor (S1NPH, S1NPL) removed. Failure to do so will result in
compressor damage.
For setting method, see the "Service Precautions" label attached to the front panel of
the outdoor unit. (Be sure to keep a record of the setting items to the "Service
Precautions" label.)
Don't touch the changeover switches (DS1-1) while setting them. Doing so may result
in malfunction.
(4)
Check whether the gas side and liquid side stop valves have been opened. Open
them if they are closed.
(5) Press
TEST (BS4)
button for 5 seconds or more to perform test operation. See About
test operation on the "Service Precautions" label for details.
Ask other installers to perform test operation or attach the front panel before having to
leave the outdoor unit working alone.
Test operation is automatically stopped after about 30 minutes (maximum 1 hour)
operation. (Perform checks of fault wiring, closed stop valves & refrigerant charging
and auto determination of piping length)
After test operation is completed, if there is no error code on the display of the remote
controller, the unit can perform normal operation 3 minutes later.
The display of the remote controller indicates symbol of test operation during this
operation.
(6) Be sure to attach the front panel of the outdoor unit after test operation is completed.
Содержание SkyAir RZR-TA Series
Страница 1: ...Service Manual Cooling Only 60 Hz Heat Pump 60 Hz RZR TA RZQ TA Series SiUS281811EA...
Страница 202: ...SiUS281811EA 196 Part 6 Service Diagnosis 5 15 Fan Motor Connector Check for FTQ TA 311...
Страница 321: ...SiUS281811EA 315 Part 7 Appendix 1 Wiring Diagrams 316 1 1 Outdoor Unit 316 1 2 Indoor Unit 320 Part 7 Appendix...
Страница 322: ...Wiring Diagrams SiUS281811EA 316 Part 7 Appendix 1 Wiring Diagrams 1 1 Outdoor Unit RZR18 24TAVJU RZQ18 24TAVJU 3D115455...
Страница 323: ...SiUS281811EA Wiring Diagrams Part 7 Appendix 317 RZR18 24TAVJUA RZQ18 24TAVJUA 3D124495...
Страница 324: ...Wiring Diagrams SiUS281811EA 318 Part 7 Appendix RZR30 36 42 48TAVJU RZQ30 36 42 48TAVJU 3D115456...
Страница 325: ...SiUS281811EA Wiring Diagrams Part 7 Appendix 319 RZR30 36 42 48TAVJUA RZQ30 36 42 48TAVJUA 3D124500...
Страница 326: ...Wiring Diagrams SiUS281811EA 320 Part 7 Appendix 1 2 Indoor Unit FCQ18 24 30 36 42 48TAVJU 3D115647A...
Страница 327: ...SiUS281811EA Wiring Diagrams Part 7 Appendix 321 FHQ18 24 30PVJU FHQ36 42MVJU 3D048116C...
Страница 328: ...Wiring Diagrams SiUS281811EA 322 Part 7 Appendix FAQ18 24TAVJU 3D114844B...
Страница 329: ...SiUS281811EA Wiring Diagrams Part 7 Appendix 323 FBQ18 24 30 36 42 48PVJU 3D065984J...