SiUS281811EA
Check
Part 6 Service Diagnosis
299
5.8 List of Inverter-Related Error Codes
CHECK 9
Code
Name
Condition for determining error
Major cause
C
ompressor current
L5
Instantaneous overcurrent of
inverter compressor
• Inverter output current exceeds 59.1 A
even instantaneously.
• Liquid sealing
• Defective compressor
• Defective inverter PCB
L8
Overcurrent of inverter
compressor
(Electronic superheating
protection sensor)
• Compressor overload running
A current of 33.5 A or more continues for a
period of consecutive 5 seconds or that of
27.6 A or more continues for a period of
consecutive 260 seconds.
• The inverter loses synchronization.
• Back-flow of compressor liquid
• Sudden changes in loads
• Disconnected compressor
wiring
• Defective PCB
Pro
tec
tion dev
ice an
d
ot
he
rs
E5
Inverter compressor lock
• The compressor is in the locked status
(does not rotate).
• Defective compressor
L1
Defective PCB (for inverter
compressor)
• No output is given.
• Defective heavy current part of
compressor
L4
Radiation fin temperature rise
• The radiation fin temperature reaches 87°C
(188°F) or more (while in operation).
• Defective fan
• Running in overload for an
extended period of time
• Defective PCB
L9
Defective startup of inverter
compressor
• The compressor motor fails to start up.
• Liquid sealing or defective
compressor
• Excessive oil or refrigerant
• Defective PCB
LC
Transmission error (between
microcomputers on the outdoor
main PCB)
• No communications are carried out across
the microcomputers on the outdoor main
PCB.
• Defective outdoor main PCB
P1
Imbalanced power supply
• Power supply voltages get significantly
imbalanced among three phases.
• Power supply error
(imbalanced voltages of 2% or
more)
• Defective PCB
• Dead PCB
P4
Defective radiation fin thermistor • The radiation fin thermistor gets short
circuited or open.
• Defective radiation fin
thermistor
U2
Power supply voltage error
• The inverter power supply voltage is high
or low.
• Power supply error
• Defective PCB
Содержание SkyAir RZR-TA Series
Страница 1: ...Service Manual Cooling Only 60 Hz Heat Pump 60 Hz RZR TA RZQ TA Series SiUS281811EA...
Страница 202: ...SiUS281811EA 196 Part 6 Service Diagnosis 5 15 Fan Motor Connector Check for FTQ TA 311...
Страница 321: ...SiUS281811EA 315 Part 7 Appendix 1 Wiring Diagrams 316 1 1 Outdoor Unit 316 1 2 Indoor Unit 320 Part 7 Appendix...
Страница 322: ...Wiring Diagrams SiUS281811EA 316 Part 7 Appendix 1 Wiring Diagrams 1 1 Outdoor Unit RZR18 24TAVJU RZQ18 24TAVJU 3D115455...
Страница 323: ...SiUS281811EA Wiring Diagrams Part 7 Appendix 317 RZR18 24TAVJUA RZQ18 24TAVJUA 3D124495...
Страница 324: ...Wiring Diagrams SiUS281811EA 318 Part 7 Appendix RZR30 36 42 48TAVJU RZQ30 36 42 48TAVJU 3D115456...
Страница 325: ...SiUS281811EA Wiring Diagrams Part 7 Appendix 319 RZR30 36 42 48TAVJUA RZQ30 36 42 48TAVJUA 3D124500...
Страница 326: ...Wiring Diagrams SiUS281811EA 320 Part 7 Appendix 1 2 Indoor Unit FCQ18 24 30 36 42 48TAVJU 3D115647A...
Страница 327: ...SiUS281811EA Wiring Diagrams Part 7 Appendix 321 FHQ18 24 30PVJU FHQ36 42MVJU 3D048116C...
Страница 328: ...Wiring Diagrams SiUS281811EA 322 Part 7 Appendix FAQ18 24TAVJU 3D114844B...