
Outline of Control (Indoor Unit)
SiUS281811EA
124
Part 4 Functions and Control
Note(s)
6. Outline of Control (Indoor Unit)
6.1 Remote
Controller
Thermistor
Temperature is controlled by both the remote controller thermistor and suction air thermistor (
∗
1)
for the indoor unit. (This is however limited to when the field setting for the remote controller
thermistor is set to Use.)
When fresh air intake kit is used, outdoor air is mixed with indoor air, and the room temperature
may not reach the set temperature, since TS and TH1 do not enter the area in which remote
controller thermistor can be used. In such case, install the remote sensor (optional accessory) in
your room, and set the field settings to not use the remote controller thermistor.
∗
FTQ-TA models do not have this control because they do not have suction air thermistor. The
thermistor is selectable manually when remote sensor (optional accessory) is installed.
Cooling
If there is a significant difference in the set temperature and the suction temperature, fine
adjustment control is carried out using a suction air thermistor (
∗
1), or using the remote controller
thermistor near the position of the user when the suction temperature is near the set temperature.
Assuming the set temperature in the figure above is 24
°
C (75
°
F), and the suction
temperature has changed from 18
°
C (64
°
F) to 30
°
C (86
°
F) (A
→
F):
(This example also assumes there are several other air conditioners, and the suction temperature
changes even when the thermostat is off.)
Suction air thermistor (
∗
1) is used for temperatures from 18°C (64°F) to 23°C (73°F) (A
→
C).
Remote controller thermistor is used for temperatures from 23°C (73°F) to 27°C (81°F) (C
→
E).
Set temperature
(Ts)
32
30
28
26
24
22
20
18
16
(°C)
(°C)
TH1 = Ts – 1
TH1 = Ts + 1
TH1 = Ts + 3
TH1 = Ts – 3
A
B
C
D
E
F
12
14 16 18 20 22 24 26 28 30 32 34
Range in which remote controller
thermistor can be used
Range in which
suction air thermistor
can be used
Suction temperature (TH1)
Differential
(°F)
(°F)
90
86
82
79
75
72
68
64
60
54
57
60
64
68
72
75
79
82
86
90
93
Содержание SkyAir RZR-TA Series
Страница 1: ...Service Manual Cooling Only 60 Hz Heat Pump 60 Hz RZR TA RZQ TA Series SiUS281811EA...
Страница 202: ...SiUS281811EA 196 Part 6 Service Diagnosis 5 15 Fan Motor Connector Check for FTQ TA 311...
Страница 321: ...SiUS281811EA 315 Part 7 Appendix 1 Wiring Diagrams 316 1 1 Outdoor Unit 316 1 2 Indoor Unit 320 Part 7 Appendix...
Страница 322: ...Wiring Diagrams SiUS281811EA 316 Part 7 Appendix 1 Wiring Diagrams 1 1 Outdoor Unit RZR18 24TAVJU RZQ18 24TAVJU 3D115455...
Страница 323: ...SiUS281811EA Wiring Diagrams Part 7 Appendix 317 RZR18 24TAVJUA RZQ18 24TAVJUA 3D124495...
Страница 324: ...Wiring Diagrams SiUS281811EA 318 Part 7 Appendix RZR30 36 42 48TAVJU RZQ30 36 42 48TAVJU 3D115456...
Страница 325: ...SiUS281811EA Wiring Diagrams Part 7 Appendix 319 RZR30 36 42 48TAVJUA RZQ30 36 42 48TAVJUA 3D124500...
Страница 326: ...Wiring Diagrams SiUS281811EA 320 Part 7 Appendix 1 2 Indoor Unit FCQ18 24 30 36 42 48TAVJU 3D115647A...
Страница 327: ...SiUS281811EA Wiring Diagrams Part 7 Appendix 321 FHQ18 24 30PVJU FHQ36 42MVJU 3D048116C...
Страница 328: ...Wiring Diagrams SiUS281811EA 322 Part 7 Appendix FAQ18 24TAVJU 3D114844B...
Страница 329: ...SiUS281811EA Wiring Diagrams Part 7 Appendix 323 FBQ18 24 30 36 42 48PVJU 3D065984J...