Field Setting from Remote Controller
SiUS281811EA
150
Part 5 Field Settings and Test Operation
12 (22)
0
Optional accessories output
selection (field selection of
output for adaptor for wiring)
Refer to the page on the right for details.
1
External ON/OFF input
(Set when ON/OFF is to be
controlled from outside.)
Refer to the page on the right for details.
2
Thermostat differential
changeover (Set when remote
sensor is to be used.)
1°C (1.8°F)
0.5°C (0.9°F)
—
—
3 (
∗
7) Airflow setting when heating
thermostat is OFF
LL tap
Set fan speed
OFF
—
4
Automatic mode differential
Refer to the page on the right for details.
5
Auto restart after power failure
OFF
ON
—
—
6 (
∗
7) Airflow setting when cooling
thermostat is OFF
LL tap
Set fan speed
OFF
—
13 (23)
0
Ceiling height setting/setting of
normal airflow
Standard
High ceiling (1)
High ceiling
(2)
—
1
Airflow direction setting
(Set when a sealing material kit
has been installed)
F (4
directions)
T (3 directions)
W (2
directions)
—
2 (
∗
6)
Swing pattern settings
All direction
synchronized
swing
—
Facing
swing
—
4
Airflow direction adjustment
range
Draft prevention
Standard
Ceiling
Soiling
prevention
—
6
External static pressure
settings
Refer to the page on the right for details.
14
(24)
4 (
∗
8) Optional kit setting (UV lamp +
humi economizer)
Refer to the page on the right for details.
5 (
∗
8)
Residential dry
Set
temperature:
room
temperature
Set temperature:
same as cooling
set temperature
—
—
15 (25)
0
Drain pump operation settings
—
ON
OFF
—
1
Humidification when heating
thermostat is OFF
Not equipped
Equipped
—
—
2 (
∗
5)
Direct duct connection
(when the indoor unit and
energy recovery ventilator are
connected by duct directly.)
Not equipped
Equipped
—
—
3
Drain pump and humidifier
interlock selection
Not
interlocked
Interlocked
—
—
5
Individual ventilation setting
— (Normal)
Individual
—
—
1b
4
Display of error codes on the
remote controller
—
Two-digit display
—
Four-digit
display
1c
0
Room temperature display
Room
temperature is
not displayed
Room
temperature is
displayed
—
—
1
Thermistor sensor for auto
changeover and setback
control by the remote controller
Utilize the return
air thermistor
Utilize the
remote
controller
thermistor
—
—
3
Access permission level setting
Level 2
Level 3
—
—
1e
2
Setback availability
N/A
Heat only
Cool only
Cool/heat
14
Setting restricted/permitted of
airflow block
Refer to the page on the right for details.
Mode
No.
(
∗
2)
First
Code
No.
Description
Second Code No.
Page
Reference
01
02
03
04
Содержание SkyAir RZR-TA Series
Страница 1: ...Service Manual Cooling Only 60 Hz Heat Pump 60 Hz RZR TA RZQ TA Series SiUS281811EA...
Страница 202: ...SiUS281811EA 196 Part 6 Service Diagnosis 5 15 Fan Motor Connector Check for FTQ TA 311...
Страница 321: ...SiUS281811EA 315 Part 7 Appendix 1 Wiring Diagrams 316 1 1 Outdoor Unit 316 1 2 Indoor Unit 320 Part 7 Appendix...
Страница 322: ...Wiring Diagrams SiUS281811EA 316 Part 7 Appendix 1 Wiring Diagrams 1 1 Outdoor Unit RZR18 24TAVJU RZQ18 24TAVJU 3D115455...
Страница 323: ...SiUS281811EA Wiring Diagrams Part 7 Appendix 317 RZR18 24TAVJUA RZQ18 24TAVJUA 3D124495...
Страница 324: ...Wiring Diagrams SiUS281811EA 318 Part 7 Appendix RZR30 36 42 48TAVJU RZQ30 36 42 48TAVJU 3D115456...
Страница 325: ...SiUS281811EA Wiring Diagrams Part 7 Appendix 319 RZR30 36 42 48TAVJUA RZQ30 36 42 48TAVJUA 3D124500...
Страница 326: ...Wiring Diagrams SiUS281811EA 320 Part 7 Appendix 1 2 Indoor Unit FCQ18 24 30 36 42 48TAVJU 3D115647A...
Страница 327: ...SiUS281811EA Wiring Diagrams Part 7 Appendix 321 FHQ18 24 30PVJU FHQ36 42MVJU 3D048116C...
Страница 328: ...Wiring Diagrams SiUS281811EA 322 Part 7 Appendix FAQ18 24TAVJU 3D114844B...
Страница 329: ...SiUS281811EA Wiring Diagrams Part 7 Appendix 323 FBQ18 24 30 36 42 48PVJU 3D065984J...