Field Setting from Remote Controller
SiUS281811EA
162
Part 5 Field Settings and Test Operation
Note(s)
1.5.20 Ceiling Height Setting, Setting of Normal Airflow
Make the following setting according to the ceiling height. The second code No. is set to
01
at the
factory.
1. The Second Code No. is factory set to Standard/All-direction airflow. For High ceiling (1) or (2),
initial setting by remote controller is required.
2. A closing member kit (optional) is required for 4-, 3-, or 2-direction airflow.
1.5.21 Airflow Direction Setting
Set the airflow direction of indoor units as given in the table below. (Set when sealing material kit of
air discharge outlet has been installed.) The second code No. is factory set to
01
.
: Factory setting
FCQ18/24TA
: Factory setting
Mode
No.
First
Code
No.
Second
Code No.
Setting
Ceiling Height
All round
outlet
4-way
Outlets
3-way
Outlets
2-way
Outlets
13
(23)
0
01
Standard
Lower than
2.7 m
(8-3/4 ft)
Lower than
3.1 m
(10-1/8 ft)
Lower than
3.0 m
(10 ft)
Lower than
3.5 m
(11-1/2 ft)
02
High Ceiling
(1)
Lower than
3.0 m
(10 ft)
Lower than
3.4 m
(11-1/8 ft)
Lower than
3.3 m
(10-3/4 ft)
Lower than
3.8 m
(12-1/2 ft)
03
High Ceiling
(2)
Lower than
3.5 m
(11-1/2 ft)
Lower than
4.0 m
(13-1/8 ft)
Lower than
3.5 m
(11-1/2 ft)
—
FCQ30/36/42/48TA
: Factory setting
Mode
No.
First
Code
No.
Second
Code
No.
Setting
Ceiling Height
All round
outlet
4-way
Outlets
3-way
Outlets
2-way
Outlets
13
(23)
0
01
Standard
Lower than
3.2 m
(10-1/2 ft)
Lower than
3.4 m
(11-1/8 ft)
Lower than
3.6 m
(12 ft)
Lower than
4.2 m
(13-3/4 ft)
02
High Ceiling
(1)
Lower than
3.6 m
(12 ft)
Lower than
3.9 m
(12-3/4 ft)
Lower than
4.0 m
(13-1/8 ft)
Lower than
4.2 m
(13-3/4 ft)
03
High Ceiling
(2)
Lower than
4.2 m
(13-3/4 ft)
Lower than
4.5 m
(14-3/4 ft)
Lower than
4.2 m
(13-3/4 ft)
—
FAQ-TA
: Factory setting
Mode
No.
First Code
No.
Second Code
No.
Contents
13 (23)
0
01
Standard
02
A little increase
03
Increase
Mode
No.
First Code
No.
Second Code
No.
Contents
13 (23)
1
01
F: 4-direction airflow
02
T: 3-direction airflow
03
W: 2-direction airflow
Содержание SkyAir RZR-TA Series
Страница 1: ...Service Manual Cooling Only 60 Hz Heat Pump 60 Hz RZR TA RZQ TA Series SiUS281811EA...
Страница 202: ...SiUS281811EA 196 Part 6 Service Diagnosis 5 15 Fan Motor Connector Check for FTQ TA 311...
Страница 321: ...SiUS281811EA 315 Part 7 Appendix 1 Wiring Diagrams 316 1 1 Outdoor Unit 316 1 2 Indoor Unit 320 Part 7 Appendix...
Страница 322: ...Wiring Diagrams SiUS281811EA 316 Part 7 Appendix 1 Wiring Diagrams 1 1 Outdoor Unit RZR18 24TAVJU RZQ18 24TAVJU 3D115455...
Страница 323: ...SiUS281811EA Wiring Diagrams Part 7 Appendix 317 RZR18 24TAVJUA RZQ18 24TAVJUA 3D124495...
Страница 324: ...Wiring Diagrams SiUS281811EA 318 Part 7 Appendix RZR30 36 42 48TAVJU RZQ30 36 42 48TAVJU 3D115456...
Страница 325: ...SiUS281811EA Wiring Diagrams Part 7 Appendix 319 RZR30 36 42 48TAVJUA RZQ30 36 42 48TAVJUA 3D124500...
Страница 326: ...Wiring Diagrams SiUS281811EA 320 Part 7 Appendix 1 2 Indoor Unit FCQ18 24 30 36 42 48TAVJU 3D115647A...
Страница 327: ...SiUS281811EA Wiring Diagrams Part 7 Appendix 321 FHQ18 24 30PVJU FHQ36 42MVJU 3D048116C...
Страница 328: ...Wiring Diagrams SiUS281811EA 322 Part 7 Appendix FAQ18 24TAVJU 3D114844B...
Страница 329: ...SiUS281811EA Wiring Diagrams Part 7 Appendix 323 FBQ18 24 30 36 42 48PVJU 3D065984J...