SiUS281811EA
Field Setting from Remote Controller
Part 5 Field Settings and Test Operation
153
1.5 Details of Field Settings for Indoor Unit
1.5.1 Filter Cleaning Sign Interval, Filter Type
When the setting 10 (20)-3 is set to
01
(Displayed), filter cleaning sign is displayed on the remote
controller after a certain period of operation time. This setting is used to change the display interval
of filter cleaning sign when the filter contamination is heavy.
The filter cleaning sign interval is determined as follows depending on the combination of Mode No.
10 (20)-0 and 10 (20)-1.
: Factory setting
: Factory setting
1.5.2 Thermistor Selection
Select a thermistor to control the room temperature.
When the unit is not equipped with an infrared floor sensor:
: Factory setting
The factory setting for the Second code No. is
01
and room temperature is controlled by the suction
air thermistor for indoor unit and remote controller thermistor. When the Second code No. is set to
02
, room temperature is controlled by the suction air thermistor. When the Second code No. is set
to
03
, room temperature is controlled by the remote controller thermistor.
When the Second Code No. is set to
02
, room temperature is controlled by the remote sensor
thermistor. When the Second Code No. is set to
03
, room temperature is controlled by the remote
controller thermistor.
Setting
10 (20)-1
01: Long life filter
02: Ultra long life filter
Filter contamination
heavy/light 10 (20)-0
Light
01
Heavy
02
Light
01
Heavy
02
Model
FCQ-TA
2,500 hrs.
1,250 hrs.
10,000 hrs.
5,000 hrs.
FHQ-P
FHQ-M
FBQ-P
FAQ-TA
200 hrs.
100 hrs.
200 hrs.
100 hrs.
Setting
10 (20)-1
01: Short interval
02: Long interval
Filter contamination
heavy/light 10 (20)-0
Light
01
Heavy
02
Light
01
Heavy
02
Model
FTQ-TA
2,500 hrs.
1,250 hrs.
10,000 hrs.
5,000 hrs.
Mode
No.
First Code
No.
Second
Code No.
Contents
10 (20)
2
01
Remote controller thermistor and suction air thermistor for
indoor unit
02
Suction air thermistor for indoor unit
03
Remote controller thermistor
FTQ-TA
: Factory setting
Mode No.
First Code No.
Second Code No.
Contents
10 (20)
2
01
—
02
Remote sensor thermistor
03
Remote controller thermistor
Содержание SkyAir RZR-TA Series
Страница 1: ...Service Manual Cooling Only 60 Hz Heat Pump 60 Hz RZR TA RZQ TA Series SiUS281811EA...
Страница 202: ...SiUS281811EA 196 Part 6 Service Diagnosis 5 15 Fan Motor Connector Check for FTQ TA 311...
Страница 321: ...SiUS281811EA 315 Part 7 Appendix 1 Wiring Diagrams 316 1 1 Outdoor Unit 316 1 2 Indoor Unit 320 Part 7 Appendix...
Страница 322: ...Wiring Diagrams SiUS281811EA 316 Part 7 Appendix 1 Wiring Diagrams 1 1 Outdoor Unit RZR18 24TAVJU RZQ18 24TAVJU 3D115455...
Страница 323: ...SiUS281811EA Wiring Diagrams Part 7 Appendix 317 RZR18 24TAVJUA RZQ18 24TAVJUA 3D124495...
Страница 324: ...Wiring Diagrams SiUS281811EA 318 Part 7 Appendix RZR30 36 42 48TAVJU RZQ30 36 42 48TAVJU 3D115456...
Страница 325: ...SiUS281811EA Wiring Diagrams Part 7 Appendix 319 RZR30 36 42 48TAVJUA RZQ30 36 42 48TAVJUA 3D124500...
Страница 326: ...Wiring Diagrams SiUS281811EA 320 Part 7 Appendix 1 2 Indoor Unit FCQ18 24 30 36 42 48TAVJU 3D115647A...
Страница 327: ...SiUS281811EA Wiring Diagrams Part 7 Appendix 321 FHQ18 24 30PVJU FHQ36 42MVJU 3D048116C...
Страница 328: ...Wiring Diagrams SiUS281811EA 322 Part 7 Appendix FAQ18 24TAVJU 3D114844B...
Страница 329: ...SiUS281811EA Wiring Diagrams Part 7 Appendix 323 FBQ18 24 30 36 42 48PVJU 3D065984J...