SiUS281811EA
Field Settings from Outdoor Unit
Part 5 Field Settings and Test Operation
179
2.6 Setting of Low Noise Operation and Demand Operation
Setting of Low Noise Operation
By connecting the external contact input to the low noise input of the external control adaptor for
outdoor unit (optional), you can lower operating noise by 2-3 dB.
When the low noise operation is automatically carried out at night (The external control
adaptor for outdoor unit is not required)
Image of operation
1.
While in setting mode 2, select the setting condition (i.e., Mode 1, Mode 2, or Mode 3) for
set item No. 22 (Setting of night-time low noise level).
2.
If necessary, while in setting mode 2, select the setting condition (i.e., 8:00 PM, 10:00
PM, or 12:00 AM) for set item No. 26 (Setting of start time of night-time low noise
operation).
(Use the start time as a guide since it is estimated according to outdoor temperatures.)
3.
If necessary, while in setting mode 2, select the setting condition (i.e., 06:00 AM, 07:00
AM, or 08:00 AM) for set item No. 27 (Setting of end time of night-time low noise
operation).
(Use the end time as a guide since it is estimated according to outdoor temperatures.)
4.
If necessary, while in setting mode 2, set the setting condition for set item No. 29 (Setting
of capacity precedence) to ON.
(If the condition is set to ON, when the air-conditioning load reaches a high level, the
system enters to normal operation mode even during night-time.)
Operation sound
Rated
Level 1
Level 2
Level 3
Time set with night-time low noise start setting
If capacity precedence is set in capacity
precedence setting, the fan speed will be
increased according to the load of air
conditioning when load is heavier.
Night-time
Time set with night-time low noise end setting
Operation sound during
night-time low noise mode
can be set with night-time
low noise level setting.
(Factory setting is OFF.)
Operation sound level set with
night-time low noise setting
Set with night-time low noise start setting.
(Factory setting is 10:00 PM.)
Set with night-time low noise end setting.
(Factory setting is 8:00 AM.)
8:00 PM
10:00 PM
12:00 AM
6:00 AM 7:00 AM 8:00 AM
Содержание SkyAir RZR-TA Series
Страница 1: ...Service Manual Cooling Only 60 Hz Heat Pump 60 Hz RZR TA RZQ TA Series SiUS281811EA...
Страница 202: ...SiUS281811EA 196 Part 6 Service Diagnosis 5 15 Fan Motor Connector Check for FTQ TA 311...
Страница 321: ...SiUS281811EA 315 Part 7 Appendix 1 Wiring Diagrams 316 1 1 Outdoor Unit 316 1 2 Indoor Unit 320 Part 7 Appendix...
Страница 322: ...Wiring Diagrams SiUS281811EA 316 Part 7 Appendix 1 Wiring Diagrams 1 1 Outdoor Unit RZR18 24TAVJU RZQ18 24TAVJU 3D115455...
Страница 323: ...SiUS281811EA Wiring Diagrams Part 7 Appendix 317 RZR18 24TAVJUA RZQ18 24TAVJUA 3D124495...
Страница 324: ...Wiring Diagrams SiUS281811EA 318 Part 7 Appendix RZR30 36 42 48TAVJU RZQ30 36 42 48TAVJU 3D115456...
Страница 325: ...SiUS281811EA Wiring Diagrams Part 7 Appendix 319 RZR30 36 42 48TAVJUA RZQ30 36 42 48TAVJUA 3D124500...
Страница 326: ...Wiring Diagrams SiUS281811EA 320 Part 7 Appendix 1 2 Indoor Unit FCQ18 24 30 36 42 48TAVJU 3D115647A...
Страница 327: ...SiUS281811EA Wiring Diagrams Part 7 Appendix 321 FHQ18 24 30PVJU FHQ36 42MVJU 3D048116C...
Страница 328: ...Wiring Diagrams SiUS281811EA 322 Part 7 Appendix FAQ18 24TAVJU 3D114844B...
Страница 329: ...SiUS281811EA Wiring Diagrams Part 7 Appendix 323 FBQ18 24 30 36 42 48PVJU 3D065984J...