SiUS281811EA
Troubleshooting by Error Codes
Part 6 Service Diagnosis
263
Reference
4.35 Refrigerant Overcharged
Error Code
F6
Applicable
Models
All outdoor units
Method of Error
Detection
Excessive charging of refrigerant is detected by using the outdoor air temperature, heat exchanger
deicer temperature and liquid pipe temperature during a check operation.
Error Decision
Conditions
During a check operation, the amount of refrigerant will be calculated based on the outdoor
temperature, the heat exchanger deicer temperature, and the liquid pipe temperature. If the
calculated amount exceeds the normal amount by 30%, too much refrigerant has been added.
(Adding only slightly more than the normal amount of refrigerant may also cause
F6
to be
displayed)
Supposed
Causes
Refrigerant overcharge
Disconnection of outdoor air thermistor, heat exchanger deicer thermistor, liquid pipe thermistor
Defective outdoor air thermistor, heat exchanger deicer thermistor, liquid pipe thermistor
Troubleshooting
CHECK 11
Refer to page 301.
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Are the above
thermistor installed on
pipes correctly?
Check the mounting condition of
the outdoor air temperature
thermistor, heat exchanger
deicer thermistor and liquid pipe
thermistor in the piping.
Remove the outdoor air
temperature thermistor, heat
exchanger deicer thermistor and
the liquid pipe thermistor from the
outdoor unit PCB and measure
resistance with a multimeter.
Rectify the overcharge of the
refrigerant.
YES
NO
NO
Replace the thermistor.
Install the thermistor correctly.
YES
Is the characteristic
of the above
thermistor normal?
CHECK 11
Содержание SkyAir RZR-TA Series
Страница 1: ...Service Manual Cooling Only 60 Hz Heat Pump 60 Hz RZR TA RZQ TA Series SiUS281811EA...
Страница 202: ...SiUS281811EA 196 Part 6 Service Diagnosis 5 15 Fan Motor Connector Check for FTQ TA 311...
Страница 321: ...SiUS281811EA 315 Part 7 Appendix 1 Wiring Diagrams 316 1 1 Outdoor Unit 316 1 2 Indoor Unit 320 Part 7 Appendix...
Страница 322: ...Wiring Diagrams SiUS281811EA 316 Part 7 Appendix 1 Wiring Diagrams 1 1 Outdoor Unit RZR18 24TAVJU RZQ18 24TAVJU 3D115455...
Страница 323: ...SiUS281811EA Wiring Diagrams Part 7 Appendix 317 RZR18 24TAVJUA RZQ18 24TAVJUA 3D124495...
Страница 324: ...Wiring Diagrams SiUS281811EA 318 Part 7 Appendix RZR30 36 42 48TAVJU RZQ30 36 42 48TAVJU 3D115456...
Страница 325: ...SiUS281811EA Wiring Diagrams Part 7 Appendix 319 RZR30 36 42 48TAVJUA RZQ30 36 42 48TAVJUA 3D124500...
Страница 326: ...Wiring Diagrams SiUS281811EA 320 Part 7 Appendix 1 2 Indoor Unit FCQ18 24 30 36 42 48TAVJU 3D115647A...
Страница 327: ...SiUS281811EA Wiring Diagrams Part 7 Appendix 321 FHQ18 24 30PVJU FHQ36 42MVJU 3D048116C...
Страница 328: ...Wiring Diagrams SiUS281811EA 322 Part 7 Appendix FAQ18 24TAVJU 3D114844B...
Страница 329: ...SiUS281811EA Wiring Diagrams Part 7 Appendix 323 FBQ18 24 30 36 42 48PVJU 3D065984J...