2
|
Troubleshooting
Service manual
42
250D7Y1B
Sky Air Advance-series
ESIE19-13A – 2020.05
2.5 Symptom based troubleshooting
2.5.1 Operation does not start
Check
Detail
When the operation lamp is off, there is
a power failure.
Check the power supply.
▪
Is the power supply breaker ON?
▪
Do other electrical appliances work?
▪
Is the rated voltage (± 10%) supplied?
▪
Check the insulation of the electric
system.
Check the type of the indoor unit.
Is the indoor unit type compatible with
the outdoor unit?
Check the transmission between indoor
and outdoor.
▪
Connection wires.
Check the outdoor air thermistor.
▪
Check the resistance of the outdoor
air thermistor.
▪
Check the connection of the outdoor
air thermistor.
When the operation lamp blinks, there
may be an error code, activating the
protection device.
Diagnose with remote controller
indication.
See
Check the operation circuit.
▪
Is the thermal fuse blown.
▪
Are wire size and wire connections
OK?.
Check fan motor.
▪
Is the magnetic switch defective?
▪
Is the overcurrent relay defective?
Check compressor.
▪
Is the contact defective?
▪
Is
the
protection
thermostat
defective?
▪
Is the compressor itself defective?
2.5.2 Operation sometimes stops
Check
Detail
When the operation lamp is off, there is
a power failure.
Check the power supply.
▪
A power failure of 2 to 10 cycles stops
air conditioner operation.
Check the outdoor air thermistor.
▪
Check the resistance of the outdoor
air thermistor.
▪
Check the connection of the outdoor
air thermistor.