3
|
Components
Service manual
132
250D7Y1B
Sky Air Advance-series
ESIE19-13A – 2020.05
c
b
a
a
f
d
e
a
Tie strap
b
Insulation
c
Thermistor wire
d
Clip
e
Thermistor
f
Thermistor holder
3
Cut and remove the insulation.
4
Pull the clip that fixes the thermistor.
5
Remove the thermistor from the thermistor holder.
6
Cut all tie straps that fix the thermistor harness.
7
Disconnect the thermistor connector from the appropriate PCB and remove
the thermistor.
INFORMATION
Some of the thermistors are wired to the same connector. See connector and pin
information of the thermistors at the start of the electrical check procedure and
151]. ALWAYS replace the complete set of thermistors wired
to the same connector.
8
When removing the complete set of thermistors wired to the same connector: