Troubleshooting
Service manual
23
250D7Y1B
Sky Air Advance-series
ESIE19-13A – 2020.05
2.4.6 E7-00 – Outdoor unit: Malfunction of outdoor unit fan motor
Trigger
Effect
Reset
Fan does NOT start
15~30 seconds after ON
signal.
It can occur that the error
code is triggered when
the fan motor is running
caused by a faulty
rotating sensor signal.
Unit will NOT stop
operating.
Automatic reset after a
continuous run.
Unit will stop operating.
Manual reset via user
interface.
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed order.
1
Perform a check of the outdoor unit fan motor. See
107].
Possible cause:
Faulty outdoor unit fan motor.
2
Perform a check of the fan inverter PCB. See
74].
Possible cause:
Faulty fan inverter PCB.
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.
2.4.7 E9-00 – Malfunction of electronic expansion valve
Trigger
Effect
Reset
No continuity of the
expansion valve.
Unit will stop operating.
Manual reset via user
interface.
Minimum expansion valve
opening and suction
superheat <4 K and
discharge superheat <5 K.
Power reset via outdoor
unit.
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed order.
1
Perform
a
check
of
all
refrigerant
side
thermistors.
See
128].
Possible cause:
Faulty refrigerant side thermistor(s).
2
Perform a check of all expansion valves. See
68].
Possible cause:
Faulty expansion valve.
3
Check that all stop valves of the refrigerant circuit are open. See