4
|
Third party components
Service manual
145
250D7Y1B
Sky Air Advance-series
ESIE19-13A – 2020.05
a
c
d
b
e
f
c
c
g
h
i
j
a
Liquid service port
b
Gas service port
c
Flexible hose
d
Manifold
e
Recovery unit
f
Vacuum pump
g
Scale
h
Recovery cylinder
i
Vacuum setup
j
Internal service port
4
Activate vacuum mode via the field settings (see field settings in installation
manual or installer reference guide).
To make sure that refrigerant cycle is completely connected and there are no
dead-zones because of closed expansion- or solenoid valves, entering the vacuum
mode ensures that:
-
all outdoor unit expansion valves get fully opened,
-
the solenoid valve gets fully opened.
5
To add refrigerant, see
142].
Is the problem solved?
Action
Yes
No further actions required.
No
Return to the troubleshooting of the
specific error and continue with the
next procedure.
To add refrigerant
1
See the installer reference guide for the correct procedure.
Is the problem solved?
Action
Yes
No further actions required.
No
Perform a pressure test of the
refrigerant circuit, see
137].