Detailed Control Functions
SiBE341001
55
Function
• RQCEQ280 ~ 848PY1
"Reverse cycle defrosting (heating oil return)" and "Partial defrosting" are available depending on the combination of the
starting condition for units of this series.
Part Name
Electric
Symbol
Partial defrosting operation
Reverse cycle defrosting (heating oil return)
Compressor M1C
124Hz
→
232 Hz
188 Hz
Outdoor unit fan
M1F
Defrost unit: OFF
Heating unit: Fan control
OFF
Electronic expansion
valve (Main)
Y1E
Defrost unit: 480 pls
Heating unit: 4 pls
→
Low pressure control
480 pls
Electronic expansion
valve (Refrigerant
charge)
Y2E
SH control
SH control
Electronic expansion
valve (Subcooling)
Y3E
By "Adjusting control of the refrigerant
amount"
By "Adjusting control of the refrigerant
amount"
Solenoid valve
(Refrigerant regulator
hot gas)
Y1S
By "Adjusting control of the refrigerant
amount"
By "Adjusting control of the refrigerant
amount"
Solenoid valve
(Refrigerant regulator
liquid pipe)
Y2S
By "Adjusting control of the refrigerant
amount"
By "Adjusting control of the refrigerant
amount"
Solenoid valve
(Refrigerant regulator
gas vent pipe)
Y3S
By "Adjusting control of the refrigerant
amount"
By "Adjusting control of the refrigerant
amount"
Solenoid valve (Hot
gas)
Y4S
ON
ON
Solenoid valve (Circuit
of oil return)
Y5S
OFF
OFF
Four way valve (Heat
exchanger switch)
Y6S
Defrost unit: OFF
Heating unit: ON
OFF
Four way valve (Dual
pressure gas pipe)
Y7S
Defrost unit: ON
Heating unit: OFF
ON
Four way valve (Mixing
unit)
Y8S
OFF
OFF
Solenoid valve (Mixing
unit inlet)
Y9S
OFF
OFF
Indoor unit fan
M1F
Thermostat ON unit: OFF
Others: No instruction
OFF
Electronic expansion
valve (Main)
Y1E
0 pls
1216 pls
→
Suction SH control
Ending condition
NO
NO
Normal heating operation
Partial defrosting operation
Reverse cycle defrosting
(heating oil return)
"Condition
to start defrosting"
has been met.
YES
YES
YES
NO
"Condition
to start heating oil
return" has been met
within 30
minutes.
"Condition
to start heating oil
return" has been
met.
End
End
[Defrost operation start conditions]
•
A lapse of every 2 hours during low-load operation
•
A lapse of every 1 hours during high-load operation
[Heating oil return operation start conditions]
•
2 hours after initial power ON
•
A lapse of every 1 ~ 2 hours during low-load operation
•
A lapse of every 8 hours during high-load operation
• Pc > 2.94 MPa
• Tb > 11˚C
• 12 min. passed
• 6 min. passed
• TsA-Te > 5˚C
• 30 sec. passed
•
&
•
OR
•
OR
&
• Pc > 2.94 MPa
• Tb > 11˚C
• 12 min. passed
• 6 min. passed
• TsA-Te > 5˚C
• 30 sec. passed
•
&
•
OR
•
OR
&
Содержание RQYQ140-180PY1
Страница 15: ...SiBE341001 Specifications 6 Part 2 Specifications 1 Specifications 7 1 1 Outdoor Units 7 1 2 BS Units 16...
Страница 215: ...SiBE341001 Piping Diagrams Appendix 206 1 Piping Diagrams 1 1 Outdoor Unit RQYQ140 180PY1 RQEQ140 180 212PY1 3d066010A...
Страница 216: ...Piping Diagrams SiBE341001 207 Appendix 1 2 BS Unit BSVQ100 160 250PV1 4D057985B...
Страница 217: ...SiBE341001 Piping Diagrams Appendix 208 BSV4Q100PV1 3D064148...
Страница 218: ...Piping Diagrams SiBE341001 209 Appendix BSV6Q100PV1 3D064149...
Страница 220: ...Wiring Diagrams for Reference SiBE341001 211 Appendix 2 2 BS Unit BSVQ100 160 250PV1 3D055928C...
Страница 221: ...SiBE341001 Wiring Diagrams for Reference Appendix 212 BSV4Q100PV1 3D063928B...
Страница 222: ...Wiring Diagrams for Reference SiBE341001 213 Appendix BSV6Q100PV1 3D063929B...
Страница 223: ...SiBE341001 Option List Appendix 214 3 Option List 3 1 Option Lists Outdoor Unit 3D066354...
Страница 224: ...Option List SiBE341001 215 Appendix...