Troubleshooting by Remote Controller
Troubleshooting
142
2.23
“
L5
”
Outdoor Unit: Momentary Overcurrent of Inverter
Compressor
Remote
Controller
Display
L5
Applicable
Models
RQYQ-PY1
RQEQ-PY1
Method of
Malfunction
Detection
Malfunction is detected from the current flowing in the power transistor.
Malfunction
Decision
Conditions
When an excessive current (59.1A) flows in the power transistor.
(Instantaneous overcurrent also causes activation.)
Supposed
Causes
Defect of compressor coil (disconnected, defective insulation)
Compressor start-up malfunction (mechanical lock)
Defect of inverter PCB