SiBE341001
Detailed Control Functions
Function
48
2.6.2 Low Pressure Protection Control
This low pressure protection control is used to protect compressors against the transient decrease of low pressure.
[In cooling operation]
★
Because of common low pressure, the following control is performed in the system.
Pe_min indicates the minimum value within the system.
Normal Operation
Pe_min < 0.34 MPa
Pe_min < 0.15 MPa
Pe_min > 0.39 MPa
Pe_min > 0.29 MPa
Pe_min < 0.07 MPa
Single type:
Compressor step of the present
situation × 0.5
Multi type:
210 Hz + OFF + OFF (upper)
Single type:
52 Hz + OFF
Multi type:
52Hz + OFF + OFF (upper limit)
Pe_min < 0.25 MPa
Hot gas solenoid valve ON
Restart standby
(3 times per 60 min. at max.)
Restart standby
(4 times per 60 min. at max.)
Stop due to malfunction
(E4 displayed)
Содержание RQYQ140-180PY1
Страница 15: ...SiBE341001 Specifications 6 Part 2 Specifications 1 Specifications 7 1 1 Outdoor Units 7 1 2 BS Units 16...
Страница 215: ...SiBE341001 Piping Diagrams Appendix 206 1 Piping Diagrams 1 1 Outdoor Unit RQYQ140 180PY1 RQEQ140 180 212PY1 3d066010A...
Страница 216: ...Piping Diagrams SiBE341001 207 Appendix 1 2 BS Unit BSVQ100 160 250PV1 4D057985B...
Страница 217: ...SiBE341001 Piping Diagrams Appendix 208 BSV4Q100PV1 3D064148...
Страница 218: ...Piping Diagrams SiBE341001 209 Appendix BSV6Q100PV1 3D064149...
Страница 220: ...Wiring Diagrams for Reference SiBE341001 211 Appendix 2 2 BS Unit BSVQ100 160 250PV1 3D055928C...
Страница 221: ...SiBE341001 Wiring Diagrams for Reference Appendix 212 BSV4Q100PV1 3D063928B...
Страница 222: ...Wiring Diagrams for Reference SiBE341001 213 Appendix BSV6Q100PV1 3D063929B...
Страница 223: ...SiBE341001 Option List Appendix 214 3 Option List 3 1 Option Lists Outdoor Unit 3D066354...
Страница 224: ...Option List SiBE341001 215 Appendix...