Troubleshooting by Remote Controller
SiBE341001
131
Troubleshooting
2.17
“
H9
”
Outdoor Unit: Malfunction of Thermistor (R1T) for
Outdoor Air
Remote
Controller
Display
H9
Applicable
Models
RQYQ-PY1
RQEQ-PY1
Method of
Malfunction
Detection
Malfunction is detected from the temperature detected by the outdoor air thermistor.
Malfunction
Decision
Conditions
When the outdoor air temperature thermistor has short circuit or open circuit.
Supposed
Causes
Defective outdoor air thermistor connection
Defect of outdoor air thermistor (R1T) for outdoor air
Defect of outdoor unit PCB (A1P)
Troubleshooting
∗
Refer to “Thermistor Resistance / Temperature Characteristics” table on P199.
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Check the connection of
connector to X18A of outdoor
PCB (A1P).
Remove the connector for the
thermistor (R1T) from the
outdoor PCB (A1P) and
measure the resistance with a
tester.
Is it normal?
Resistance is normal?
NO
NO
YES
YES
Connect the connector correctly.
Replace the outdoor air thermistor
(R1T).
Replace the outdoor unit PCB
(A1P).
Содержание RQYQ140-180PY1
Страница 15: ...SiBE341001 Specifications 6 Part 2 Specifications 1 Specifications 7 1 1 Outdoor Units 7 1 2 BS Units 16...
Страница 215: ...SiBE341001 Piping Diagrams Appendix 206 1 Piping Diagrams 1 1 Outdoor Unit RQYQ140 180PY1 RQEQ140 180 212PY1 3d066010A...
Страница 216: ...Piping Diagrams SiBE341001 207 Appendix 1 2 BS Unit BSVQ100 160 250PV1 4D057985B...
Страница 217: ...SiBE341001 Piping Diagrams Appendix 208 BSV4Q100PV1 3D064148...
Страница 218: ...Piping Diagrams SiBE341001 209 Appendix BSV6Q100PV1 3D064149...
Страница 220: ...Wiring Diagrams for Reference SiBE341001 211 Appendix 2 2 BS Unit BSVQ100 160 250PV1 3D055928C...
Страница 221: ...SiBE341001 Wiring Diagrams for Reference Appendix 212 BSV4Q100PV1 3D063928B...
Страница 222: ...Wiring Diagrams for Reference SiBE341001 213 Appendix BSV6Q100PV1 3D063929B...
Страница 223: ...SiBE341001 Option List Appendix 214 3 Option List 3 1 Option Lists Outdoor Unit 3D066354...
Страница 224: ...Option List SiBE341001 215 Appendix...