Detailed Control Functions
SiBE341001
39
Function
2.5
Normal Operation
2.5.1 List of Functions in Normal Operation
<Outdoor Unit>
<Indoor Unit>
<BS Unit>
Part Name
Electric
Symbol
Normal Cooling
Normal Heating
Normal Simultaneous
Cooling / Heating
Compressor M1C
PI control, High pressure
protection, Low pressure
protection, Td protection,
INV protection
PI control, High pressure
protection, Low pressure
protection, Td protection,
INV protection
PI control, High pressure
protection, Low pressure
protection, Td protection,
INV protection
Outdoor unit fan
M1F
Cooling fan control
• Outdoor unit heat
exchanger: Condenser /
Cooling fan control
• Outdoor unit heat
exchanger: Evaporator /
Fan step 7 or 8
• Outdoor unit heat
exchanger: Condenser /
Cooling fan control
• Outdoor unit heat
exchanger: Evaporator /
Fan step 7 or 8
Electronic expansion valve
(Main)
Y1E
480 pls
• Outdoor unit heat
exchanger: Condenser /
Liquid pressure control
• Outdoor unit heat
exchanger: Evaporator /
PI control
• Outdoor unit heat
exchanger: Condenser /
Liquid pressure control
• Outdoor unit heat
exchanger: Evaporator /
PI control
Electronic expansion valve
(Subcooling)
Y3E
PI control
PI control
PI control
Electronic expansion valve
(Refrigerant charge)
Y2E
41 pls for refrigerant
discharge
41 pls for refrigerant
discharge
41 pls for refrigerant
discharge
Solenoid valve (Refrigerant
regulator hot gas)
Y1S
ON for refrigerant
discharge
ON for refrigerant
discharge
ON for refrigerant
discharge
Solenoid valve (Refrigerant
regulator liquid pipe)
Y2S
ON for refrigerant
recovery
ON for refrigerant
recovery
ON for refrigerant
recovery
Solenoid valve (Refrigerant
regulator gas vent pipe)
Y3S
ON for refrigerant
recovery
ON for refrigerant
recovery
ON for refrigerant
recovery
Solenoid valve (Hot gas)
Y4S
OFF
OFF
OFF
Solenoid valve (Circuit of oil
return)
Y5S
ON
ON
ON
Four way valve (Heat
exchanger switch)
Y6S
OFF
• Outdoor unit heat
exchanger: Condenser /
OFF
• Outdoor unit heat
exchanger: Evaporator /
ON
• Outdoor unit heat
exchanger: Condenser /
OFF
• Outdoor unit heat
exchanger: Evaporator /
ON
Four way valve (Dual
pressure gas pipe)
Y7S
ON
OFF
OFF
Four way valve (Mixing unit)
Y8S
OFF
OFF
OFF
Solenoid valve (Mixing unit
inlet)
Y9S
OFF
OFF
OFF
Part Name
Electric
Symbol
Normal cooling
Normal heating
Thermostat
ON unit
Thermostat
OFF unit
Stopping
unit
Thermostat
ON unit
Thermostat
OFF unit
Stopping
unit
Indoor unit fan
M1F
Remote
controller
setting
Remote
controller
setting
OFF
Remote
controller
setting
LL
OFF
Electronic expansion valve
(Main)
Y1E
Normal
opening
0 pls
0 pls
Normal
opening
192 pls
192 pls
Part Name
Electric
Symbol
Normal cooling
Normal heating
Electronic expansion valve
(EVSC)
Y1E
0 pls
0 pls
Electronic expansion valve
(EVHS)
Y2E
480 pls ( fully opened )
480 pls ( fully opened )
Electronic expansion valve
(EVLS)
Y3E
480 pls ( fully opened )
0 pls
Electronic expansion valve
(EVH)
Y4E
760 pls ( fully opened )
760 pls ( fully opened )
Electronic expansion valve
(EVL)
Y5E
760 pls ( fully opened )
0 pls
Содержание RQYQ140-180PY1
Страница 15: ...SiBE341001 Specifications 6 Part 2 Specifications 1 Specifications 7 1 1 Outdoor Units 7 1 2 BS Units 16...
Страница 215: ...SiBE341001 Piping Diagrams Appendix 206 1 Piping Diagrams 1 1 Outdoor Unit RQYQ140 180PY1 RQEQ140 180 212PY1 3d066010A...
Страница 216: ...Piping Diagrams SiBE341001 207 Appendix 1 2 BS Unit BSVQ100 160 250PV1 4D057985B...
Страница 217: ...SiBE341001 Piping Diagrams Appendix 208 BSV4Q100PV1 3D064148...
Страница 218: ...Piping Diagrams SiBE341001 209 Appendix BSV6Q100PV1 3D064149...
Страница 220: ...Wiring Diagrams for Reference SiBE341001 211 Appendix 2 2 BS Unit BSVQ100 160 250PV1 3D055928C...
Страница 221: ...SiBE341001 Wiring Diagrams for Reference Appendix 212 BSV4Q100PV1 3D063928B...
Страница 222: ...Wiring Diagrams for Reference SiBE341001 213 Appendix BSV6Q100PV1 3D063929B...
Страница 223: ...SiBE341001 Option List Appendix 214 3 Option List 3 1 Option Lists Outdoor Unit 3D066354...
Страница 224: ...Option List SiBE341001 215 Appendix...