20
Product description
EN
RoCon UFH
Table 4-6: Technical specifications for actuators
Daikin recommends the use of Daikin UFH-Sat8 actuators to ensure optimum system
performance. If actuators from other manufacturers are used, the following limit val-
ues must be met:
Operating voltage
AC 230 V ±10 %, 50/60 Hz
Max. operating current
9 mA
Max. inrush current
140 mA / 200 ms
Max. operating power
2 W
Special characteristic
Short-circuit proof, protected against overvolt-
age
Actuators of other manufacturers
connected per control circuit
Max. 2
Содержание RoCon UFH
Страница 2: ......
Страница 27: ...25 Mounting EN RoCon UFH 6 Refit the cover and close it Fig 5 5 Closing the cover ...
Страница 64: ......
Страница 89: ...25 Montage DE RoCon UFH 6 Hängen Sie die Abdeckung ein und schließen diese Bild 5 5 Abdeckung schließen ...
Страница 126: ......
Страница 151: ...25 Montage FR RoCon UFH 6 Accrocher le couvercle et le fermer Fig 5 5 Fermer le couvercle ...
Страница 188: ......
Страница 213: ...25 Montage NL RoCon UFH 6 Haak de afdekking vast en sluit haar Afb 5 5 Afdekking sluiten ...
Страница 250: ......
Страница 275: ...25 Installazione IT RoCon UFH 6 Agganciare la copertura e chiuderla Fig 5 5 Chiusura della copertura ...
Страница 312: ...008 1706699 00 12 2020 Copyright Daikin www daikin eu ...