22
Product description
EN
RoCon UFH
4.6
Information on RoCon UFH as per EN 60730-1:2016
•
RoCon UFH is an electronic control type C as per EN 60730-1.
•
RoCon UFH is suitable for continuous operation.
•
The type of disconnection of the actuators and pumps is micro disconnection.
•
The PTI value of the insulation (PCBs) is 175.
•
RoCon UFH corresponds to installation category 3.
•
RoCon UFH corresponds to overvoltage category 2.
•
The limit value for the SELV circuit is DC 5 V.
•
The maximum permissible click rate is 1/minute.
•
The test voltage for the EMC noise immunity tests is ±1 kV (±2 kV).
4.7
Information on RoCon UFH as per EN 15500:2017
•
Type: Fixed point function.
•
Zone type: Constant conditions.
•
Application groups: Individual zone control equipment.
•
Output types: On/off actuators.
•
Sensor type: NTC ±5 %.
•
Certified value of control accuracy: 0.6 K (0.5 K).
Содержание RoCon UFH
Страница 2: ......
Страница 27: ...25 Mounting EN RoCon UFH 6 Refit the cover and close it Fig 5 5 Closing the cover ...
Страница 64: ......
Страница 89: ...25 Montage DE RoCon UFH 6 Hängen Sie die Abdeckung ein und schließen diese Bild 5 5 Abdeckung schließen ...
Страница 126: ......
Страница 151: ...25 Montage FR RoCon UFH 6 Accrocher le couvercle et le fermer Fig 5 5 Fermer le couvercle ...
Страница 188: ......
Страница 213: ...25 Montage NL RoCon UFH 6 Haak de afdekking vast en sluit haar Afb 5 5 Afdekking sluiten ...
Страница 250: ......
Страница 275: ...25 Installazione IT RoCon UFH 6 Agganciare la copertura e chiuderla Fig 5 5 Chiusura della copertura ...
Страница 312: ...008 1706699 00 12 2020 Copyright Daikin www daikin eu ...