INTRODUCTION

ED 19129-1

WWW.DAIKINAPPLIED.COM

Introduction

This manual describes how to integrate a MicroTech

®

 MT2300 

SmartSource WSHP unit controller to a BAS (building 

automation system) for network communication . 

Description

The MicroTech application supports SmartSource

®

 Single/

Two Stage and Dual Compressor R32 models with MT2300 

controls .
The MicroTech controller supports the BACnet

®

 MS/TP 

standard protocol . A separate BACnet communication module 

must be attached to the unit controller for network integration .  
BACnet network parameters include heating/cooling/

dehumidification setpoints, system status, fan and compressor 

operation, monitoring, and alarm objects . Once the unit has 

been configured as described in the 

Network Configuration

 

section, BACnet objects are accessible from the BAS .
It is assumed that the user is familiar with BACnet integration . 

Contact the Daikin Applied Controls Customer Support group 

at 866-462-7829 or Controls@daikinapplied .com for additional 

assistance, if necessary .

Software Version

This document supports the latest version of the MicroTech 

application and all subsequent versions until otherwise 

indicated . If the MicroTech application software is a later 

version, some of the information in this document may not 

apply . 
The software version can be read from the Application_

Software_Version property of the BACnet Device Object .

Hazardous Information Messages

 DANGER

Danger indicates a hazardous situation, which will result in death or serious 

injury if not avoided.

 WARNING

Warning indicates a potentially hazardous situations, which can result in 

property damage, personal injury, or death if not avoided.

 CAUTION

Caution indicates a potentially hazardous situations, which can result in 

minor injury or equipment damage if not avoided.

NOTICE

Notice indicates practices not related to physical injury.

Reference Documents

Title

Number

Company

Source

SmartSource with 

MicroTech Unit Controller 

Operation Manual

OM 1364

Daikin Applied

www .

DaikinApplied .

com

MicroTech SmartSource 

BACnet Communication 

Module Installation 

Manual

IM 1363

Daikin Applied

www .

DaikinApplied .

com

BACnet A Data 

Communication Protocol 

for Building Automation 

and Control Networks

ANSI/ 

ASHRAE 

135-2006

American Society 

of Heating, 

Refrigeration, and 

Air-Conditioning 

Engineers

www .ashrae .org

BACnet Networks

BACnet is a standard communication protocol for Building 

Automation and Control Networks developed by the American 

National Standards Institute (ANSI) and American Society 

of Heating, Refrigeration and Air-conditioning Engineers 

(ASHRAE) specified in ANSI/ASHRAE standard 135-2012 

(

www .ashrae .org

) . It addresses all aspects of the various 

systems that are applied to building control systems . BACnet 

provides the communication infrastructure needed to integrate 

products manufactured by different vendors and to integrate 

building services that are now independent .

BACnet Network Compatibility

The WSHP unit controller is tested according to the BACnet 

Testing Laboratory (BTL) Test Plan . It is designed to meet the 

requirements of the most current BACnet Standard as stated 

in the Protocol Implementation and Conformance Statement 

(PICS) .  However, it is not BTL listed . See 

BACnet PICS .

BACnet Device Object Types 

The MicroTech WSHP unit controller incorporates standard 

BACnet object types (i.e., object types defined in the BACnet 

Standard) that conform to the BACnet Standard . Each object 

has properties that control unit variables . Some object types 

occur more than once in the unit controller; each occurrence 

or instance has different properties and controls different unit 

variables . Each instance is designated with a unique type and 

instance index . Some properties can be adjusted (read/write 

properties such as temperature setpoints) from the network 

and others can only be interrogated (read-only properties such 

as status information) .

Device Object Properties

Each BACnet compatible device can only have a single 

BACnet Device Object . The Device Object contains other 

informative properties as shown in

 

Table 1 .

 Also see 

BACnet 

PICS

 .

Содержание MICROTECH SMARTSOURCE 2300 WSHP

Страница 1: ...00 WSHP UNIT CONTROLLER MODELS SCH SDH SMH SNH AND SSH STH WITH R32 REFRIGERANT SCH SDH SMH SNH AND SSH STH LEARN MORE AT DAIKINAPPLIED COM MICROTECH SMARTSOURCE WSHP BACNET NETWORK INTEGRATION GUIDE...

Страница 2: ...pported 26 Device Management 26 Segmentation Capability 26 Data Link Layer Options 26 Device Address Binding 26 Character Sets Supported 26 Standard Object Types Supported 27 Revision History 28 2024...

Страница 3: ...Controller Operation Manual OM 1364 Daikin Applied www DaikinApplied com MicroTech SmartSource BACnet Communication Module Installation Manual IM 1363 Daikin Applied www DaikinApplied com BACnet A Da...

Страница 4: ...ng Vendor Identifier 120 3 Unsigned 16 Model Name 70 SmartSource Series2 MT2300_WSHP_Ser2 Character String SmartSource SS2C MT2300_WSHP_SS2C Firmware Revision 44 SmartSource Series2 HP4 v2 0 Character...

Страница 5: ...u Figure 1 The BACnet configuration menu is accessed using a serial application like Windows HyperTerminal or PuTTY It is assumed that the user is familiar with such an application Addressing must be...

Страница 6: ...ter to the BACnet communication module 3 Once connected press the Enter key to display the menu shown in Figure 1 4 Use the BACnet configuration menu to change the terminal EIA 232 baud rate if requir...

Страница 7: ...is requested then the communication module s non volatile memory is set to default values A cold reset can also be performed by the following button sequence on the BACnet communication module 1 Pres...

Страница 8: ...ischarge air temperature sensor value if installed and configured with a valid input 3 Local Setpoint Adjust AI 5 LocalSetpt 55 to 95 F 12 78 to 35 C Default 32 F 0 C R N Reflects the value of the sel...

Страница 9: ...disables this feature Interstage OFF Timer AV 8 cpIntStgOffTmr 0 to 1200 sec Default 0 W Y A countdown timer that defines the minimum period of time between turn off of the subsequent heating and cool...

Страница 10: ...r reboot Network Temperature Setpoint AV 19 NetworkSetpoint 50 to 95 F 10 to 35 C Default6 621 806 F 327 67 C C N Allows the network to set the reference setpoint in occupied and standby occupancy mod...

Страница 11: ...lt 28 F 2 22 C W Y Value of the low entering water temperature EWT setpoint when using a glycol loop fluid Low EWT Setpoint for Water AV 31 cpLowEwtSptWtr 40 to 65 F 4 44 to 18 34 C Default 55 F 12 78...

Страница 12: ...the isolation valve output energizes allowing the supply water flow timer to expire Local Space Dewpoint AV 50 LocalDewpointCalc 32 to 150 F 0 to 65 55 C Default Null6 R N Reflects the local space de...

Страница 13: ...ystemMinInstance the Present Value is writeable and it has a default value of 3101000 During the commissioning process the present value of AV412 is added to the MAC Address to determine the Device In...

Страница 14: ...rst stage cooling 1 Active Thermostat switch is closed indicating first stage cooling is active Thermostat Cooling Stage 2 BI 9 Tstat_Y2 0 Inactive 1 Active Thermostat input for cooling Applies when u...

Страница 15: ...esent 1 On I O expansion module is required Compressor Availability SmartSource SS2C BI 21 BB_ConfigSw7 0 Off 1 On Configuration switches 7 and 8 settings for compressor availabillity Applies to Smart...

Страница 16: ...Fan main command is On Fan Speed BO 4 FanLowOut R Fan speed output command status Applies only when the Fan Main output command is On 0 Fan high speed command is On 1 Fan low speed command is On Pump...

Страница 17: ...ensor input or space dewpoint Fan Run Status MSI 5 FanRunStatus 1 Fan is Off 2 Fan is On R N Commanded fan run status Used in conjunction with fan speed command AV 38 to indicate fan speed status Para...

Страница 18: ...tion mode Auto Off Heat Cool Dehumidification or Fan Only Application Mode does not force the unit into any state However it does disable certain unit operations Examples 1 Application Mode of Cool di...

Страница 19: ...teable C Commandable Table 10 Device Object Properties Point Name Object Type Instance BACnet Object Name Range Default in Units Read Write Access2 Non volatile Memory1 Description Description Device...

Страница 20: ...n alarm is cleared but the alarm condition still exists the controller immediately re activates the alarm NOTE Cycling power to the unit controller resets the fault alarm Intelligent Alarm Reset The M...

Страница 21: ...sure 27 Cmp1 Hi Disch Temp Compressor 1 High Discharge Temperature Manual Yes Compressor high and low pressure switches have both opened simultaneously indicating a compressor high discharge temperatu...

Страница 22: ...y 26 WSE Low Temp Cutout Waterside Economizer Low Temperature Cutout Auto No Alarm indicates a low EWT condition Applies to units that have a waterside economizer with an active request for cooling 1...

Страница 23: ...ion parameters Table 13 Occupancy Parameters Parameter Description EffectOccup MSV 6 Indicates the actual occupancy mode of the unit Occupied Unoccupied Bypass Standby OccManCmd MSV 7 Network occupanc...

Страница 24: ...ffective Heat ON SP 60 F AV35 0 5 F Deadband Factor 75 70 2 2 5 Effective Cool ON SP 77 3 80 F Effective Heat OFF SP 60 2 62 F Reference SP 72 0 5 72 5 F Effective Cool ON SP 72 5 2 5 75 F Effective C...

Страница 25: ...P EffCoolOnSP AV10 EffHeatOnSP AV4 AV24 EffHeatOffSP EffHeatOnSP AV10 5 The unit is operating in Standby mode with Short Range Local Setpoint Adjust selected and MSV14 2 EffCoolOnSP HP1 AV2 AV25 EffCo...

Страница 26: ...BACnet Smart Sensor B SS BACnet Smart Actuator B SA BACnet Interoperability Building Blocks Supported Data Sharing Data Sharing Read Property B DS RP B Data Sharing Read Property Multiple B DS RPM B...

Страница 27: ...COV_Increment Present_Value Priority_Array Relinquish_Default Binary Input Active_Text Description Inactive_Text Binary Value Active_Text Description Inactive_Text Present_Value Multi state Input Sta...

Страница 28: ...and WSHP single two stage and dual compressor applications including the following Added analog value network points for monitoring and control of relative humidity Added analog value network points f...

Страница 29: ...S COILS CONDENSING UN I T S A IR HANDLERS WATER COOLED CHILLERS AIR COOLED CHI L L ER S MOD U LAR CENTRAL PLANTS SITELINE BUILDING CONTROL S UNIT HEATERS FAN COILS AIR PURIFIERS WATER SOURCE HEAT PUMP...

Страница 30: ...ANDLERS WATER COOLED CHILLERS AIR COOLED CHI L L ER S MOD U LAR CENTRAL PLANTS SITELINE BUILDING CONTROL S UNIT HEATERS FAN COILS AIR PURIFIERS WATER SOURCE HEAT PUMPS VARIABLE AIR VOLUME UNITS UNIT V...

Отзывы: