BACNET DATA TABLES

MT2300 WSHP BACNET INTEGRATION

DAIKIN  APPLIED

12 

Table 4: Analog Values, Continued

Point Name

Object 

Type/

Instance

BACnet Object 

Name

Range/Default 

 

(in Units)

Read/

Write 

Access

2

Non-

volatile 

Memory

1

Description

Compressor 1 Starts 

AV:41

CompStarts 

0 to 65535 Starts

W

Y

Total number of compressor starts .

8

Compressor 2 / 

Compressor High 

Capacity Run Hours

AV:42

Comp2RunHours / 

CompHiCapRunHours  0 to 65535 Hours

W

Y

Total runtime hours for compressor high capacity 

or compressor 2 runtime hours, depending on 

application .

8

Compressor 2 / 

Compressor  High 

Capacity Starts

AV:43

Comp2Starts /

CompHiCapStarts

0 to 65535 Starts

W

Y

Total number of high capacity compressor starts or 

compressor 2 starts, depending on application .

8

Effective Space Humidity

AV:44

EffectSpaceRH

0 to 100%

R

N

The indoor humidity value provided by a valid 

network input or local sensor . It represents the 

network space relative humidity value (AV:45), if 

available . Otherwise, it represents the humidity 

sensor input provided by the indoor relative humidity 

value .

Network Space Humidity  

Override

AV:45

NetworkSpaceRH

0 to 100%

Default: Null

6

C

N

Provides an indoor humidity value from the network 

instead of using the local humidity sensor . The 

network override reverts back to its default value 

upon unit controller reset . 

Space Humidity Setpoint 

Differential

AV:46

cpSpaceRH_Diff

1 to 20%

5%

W

Y

Space relative humidity setpoint differential used to 

determine the effective “off” setpoint from the “on” 

setpoint .

Space Humidity Setpoint

AV:47

cpSpaceRH_Setpt

0 to 100%

Default: 50% 

W

Y

Configures the space relative humidity setpoint value. 

This setpoint initiates dehumidification on units that 

are properly configured and have dehumidification 

enabled .

Effective Control 

Temperature

AV:48

EffectControlTemp

0 to 158°F

-17 .77 to 70°C

R

N

Effective control temperature (space, return, 

or average of the two) used to determine the 

temperature at which the unit should heat or cool .

Compressor Wait for 

Flow Timer

AV:49

cpWaitForFlow

45 to 90 sec

Default: 60 sec

W

Y

Sets the amount of time the compressor is prevented 

from running after the isolation valve output 

energizes, allowing the supply water flow timer to 

expire .

Local Space Dewpoint

AV:50

LocalDewpointCalc

32 to 150°F

0 to 65.55ºC

Default: Null

6

R

N

Reflects the local space dewpoint calculated value. 

The calculation uses the effective space relative 

humidity value in conjunction with effective space 

temperature value . 

Network Dewpoint 

Override

AV:51

NetworkDewpoint

32 to 150°F

0 to 65.55ºC

Default: Null

6

C

N

Network dewpoint override . Provides an indoor 

dewpoint value from the network instead of using 

the calculated local space dewpoint input . The 

network override reverts to its default value upon unit 

controller reset .

Effective Dewpoint

AV:52

EffectiveDewpoint

32 to 150°F

0 to 65.55ºC

Default: Null

6

R

N

Effective dewpoint. It represents the network 

input (AV:51), if available and valid . Otherwise, it 

represents the calculated local space dewpoint input 

(AV:50) .

Dewpoint Setpoint

AV:53

cpDewpointSetp

40 to 60°F

4 .44 to 15 .56°C 

Default: 

49°F / 9 .44°C

W

Y

Dewpoint setpoint used for dehumidification control. 

Requires a relative humidity sensor with valid input .

Dewpoint Differential

AV:54

cpDewpointDiff

1 to 5°F

0 .55 to 2 .78°C

Default: 

 2°F / 1 .1°C

W

Y

Dewpoint setpoint differential value. Used when 

calculating the effective dewpoint “off” setpoint from 

the “on” setpoint .

Variable Fan Speed 

PWM - Fan-Only

AV:55

cpVsFanOnlyPWM

10 to 100%

Default: 20%

W

Y

Variable fan speed PWM output when unit is in 

fan-only state . Applies when network PWM fan 

configuration enable (MSV:17) is enabled.

Variable Fan Speed 

PWM - Dehumidification

AV:56

cpVsDehumPWM

50 to 100% 

Default: 70%

W

Y

Variable fan speed PWM output for dehumidification. 

Applies when network PWM fan configuration enable 

(MSV:17) is enabled .

Variable Fan Speed 

PWM - Cool Stage 1

AV:57

cpVsCool1PWM

50 to 100% 

Default: 80%

W

Y

Variable fan speed PWM output for cooling stage 1 . 

Applies when network PWM fan configuration enable 

(MSV:17) is enabled .

Variable Fan Speed 

PWM -Cool Stage 2

AV:58

cpVsCool2PWM

50 to 100% 

Default: 100%

W

Y

Variable fan speed PWM output for cooling stage 2 . 

Applies when network PWM fan configuration enable 

(MSV:17) is enabled .

Variable Fan Speed 

PWM - Heat Stage 1

AV:59

cpVsHeat1PWM

50 to 100% 

Default: 80%

W

Y

Variable fan speed PWM output for heating stage 1 . 

Applies when network PWM fan configuration enable 

(MSV:17) is enabled .

Содержание MICROTECH SMARTSOURCE 2300 WSHP

Страница 1: ...00 WSHP UNIT CONTROLLER MODELS SCH SDH SMH SNH AND SSH STH WITH R32 REFRIGERANT SCH SDH SMH SNH AND SSH STH LEARN MORE AT DAIKINAPPLIED COM MICROTECH SMARTSOURCE WSHP BACNET NETWORK INTEGRATION GUIDE...

Страница 2: ...pported 26 Device Management 26 Segmentation Capability 26 Data Link Layer Options 26 Device Address Binding 26 Character Sets Supported 26 Standard Object Types Supported 27 Revision History 28 2024...

Страница 3: ...Controller Operation Manual OM 1364 Daikin Applied www DaikinApplied com MicroTech SmartSource BACnet Communication Module Installation Manual IM 1363 Daikin Applied www DaikinApplied com BACnet A Da...

Страница 4: ...ng Vendor Identifier 120 3 Unsigned 16 Model Name 70 SmartSource Series2 MT2300_WSHP_Ser2 Character String SmartSource SS2C MT2300_WSHP_SS2C Firmware Revision 44 SmartSource Series2 HP4 v2 0 Character...

Страница 5: ...u Figure 1 The BACnet configuration menu is accessed using a serial application like Windows HyperTerminal or PuTTY It is assumed that the user is familiar with such an application Addressing must be...

Страница 6: ...ter to the BACnet communication module 3 Once connected press the Enter key to display the menu shown in Figure 1 4 Use the BACnet configuration menu to change the terminal EIA 232 baud rate if requir...

Страница 7: ...is requested then the communication module s non volatile memory is set to default values A cold reset can also be performed by the following button sequence on the BACnet communication module 1 Pres...

Страница 8: ...ischarge air temperature sensor value if installed and configured with a valid input 3 Local Setpoint Adjust AI 5 LocalSetpt 55 to 95 F 12 78 to 35 C Default 32 F 0 C R N Reflects the value of the sel...

Страница 9: ...disables this feature Interstage OFF Timer AV 8 cpIntStgOffTmr 0 to 1200 sec Default 0 W Y A countdown timer that defines the minimum period of time between turn off of the subsequent heating and cool...

Страница 10: ...r reboot Network Temperature Setpoint AV 19 NetworkSetpoint 50 to 95 F 10 to 35 C Default6 621 806 F 327 67 C C N Allows the network to set the reference setpoint in occupied and standby occupancy mod...

Страница 11: ...lt 28 F 2 22 C W Y Value of the low entering water temperature EWT setpoint when using a glycol loop fluid Low EWT Setpoint for Water AV 31 cpLowEwtSptWtr 40 to 65 F 4 44 to 18 34 C Default 55 F 12 78...

Страница 12: ...the isolation valve output energizes allowing the supply water flow timer to expire Local Space Dewpoint AV 50 LocalDewpointCalc 32 to 150 F 0 to 65 55 C Default Null6 R N Reflects the local space de...

Страница 13: ...ystemMinInstance the Present Value is writeable and it has a default value of 3101000 During the commissioning process the present value of AV412 is added to the MAC Address to determine the Device In...

Страница 14: ...rst stage cooling 1 Active Thermostat switch is closed indicating first stage cooling is active Thermostat Cooling Stage 2 BI 9 Tstat_Y2 0 Inactive 1 Active Thermostat input for cooling Applies when u...

Страница 15: ...esent 1 On I O expansion module is required Compressor Availability SmartSource SS2C BI 21 BB_ConfigSw7 0 Off 1 On Configuration switches 7 and 8 settings for compressor availabillity Applies to Smart...

Страница 16: ...Fan main command is On Fan Speed BO 4 FanLowOut R Fan speed output command status Applies only when the Fan Main output command is On 0 Fan high speed command is On 1 Fan low speed command is On Pump...

Страница 17: ...ensor input or space dewpoint Fan Run Status MSI 5 FanRunStatus 1 Fan is Off 2 Fan is On R N Commanded fan run status Used in conjunction with fan speed command AV 38 to indicate fan speed status Para...

Страница 18: ...tion mode Auto Off Heat Cool Dehumidification or Fan Only Application Mode does not force the unit into any state However it does disable certain unit operations Examples 1 Application Mode of Cool di...

Страница 19: ...teable C Commandable Table 10 Device Object Properties Point Name Object Type Instance BACnet Object Name Range Default in Units Read Write Access2 Non volatile Memory1 Description Description Device...

Страница 20: ...n alarm is cleared but the alarm condition still exists the controller immediately re activates the alarm NOTE Cycling power to the unit controller resets the fault alarm Intelligent Alarm Reset The M...

Страница 21: ...sure 27 Cmp1 Hi Disch Temp Compressor 1 High Discharge Temperature Manual Yes Compressor high and low pressure switches have both opened simultaneously indicating a compressor high discharge temperatu...

Страница 22: ...y 26 WSE Low Temp Cutout Waterside Economizer Low Temperature Cutout Auto No Alarm indicates a low EWT condition Applies to units that have a waterside economizer with an active request for cooling 1...

Страница 23: ...ion parameters Table 13 Occupancy Parameters Parameter Description EffectOccup MSV 6 Indicates the actual occupancy mode of the unit Occupied Unoccupied Bypass Standby OccManCmd MSV 7 Network occupanc...

Страница 24: ...ffective Heat ON SP 60 F AV35 0 5 F Deadband Factor 75 70 2 2 5 Effective Cool ON SP 77 3 80 F Effective Heat OFF SP 60 2 62 F Reference SP 72 0 5 72 5 F Effective Cool ON SP 72 5 2 5 75 F Effective C...

Страница 25: ...P EffCoolOnSP AV10 EffHeatOnSP AV4 AV24 EffHeatOffSP EffHeatOnSP AV10 5 The unit is operating in Standby mode with Short Range Local Setpoint Adjust selected and MSV14 2 EffCoolOnSP HP1 AV2 AV25 EffCo...

Страница 26: ...BACnet Smart Sensor B SS BACnet Smart Actuator B SA BACnet Interoperability Building Blocks Supported Data Sharing Data Sharing Read Property B DS RP B Data Sharing Read Property Multiple B DS RPM B...

Страница 27: ...COV_Increment Present_Value Priority_Array Relinquish_Default Binary Input Active_Text Description Inactive_Text Binary Value Active_Text Description Inactive_Text Present_Value Multi state Input Sta...

Страница 28: ...and WSHP single two stage and dual compressor applications including the following Added analog value network points for monitoring and control of relative humidity Added analog value network points f...

Страница 29: ...S COILS CONDENSING UN I T S A IR HANDLERS WATER COOLED CHILLERS AIR COOLED CHI L L ER S MOD U LAR CENTRAL PLANTS SITELINE BUILDING CONTROL S UNIT HEATERS FAN COILS AIR PURIFIERS WATER SOURCE HEAT PUMP...

Страница 30: ...ANDLERS WATER COOLED CHILLERS AIR COOLED CHI L L ER S MOD U LAR CENTRAL PLANTS SITELINE BUILDING CONTROL S UNIT HEATERS FAN COILS AIR PURIFIERS WATER SOURCE HEAT PUMPS VARIABLE AIR VOLUME UNITS UNIT V...

Отзывы: