NETWORK CONFIGURATION
MT2300 WSHP BACNET INTEGRATION
DAIKIN APPLIED
6
The BACnet Configuration Menu
The BACnet communication module’s configuration menu is
accessed through the DB-9 serial connector on the module
itself . Any serial terminal device or application (such as
Windows HyperTerminal) can be used to view the menu and
change the configuration parameters.
Follow these steps to connect to the BACnet configuration
menu (
):
1 . Verify that the terminal application communication
settings are set to: 19200 bps, 8-data bits, 1-stop bit, no
parity, and no flow control.
2 . Use a null modem serial cross over cable to connect the
computer to the BACnet communication module .
3 . Once connected, press the ‘Enter’ key to display the
4 .
Use the BACnet configuration menu to change the
terminal EIA-232 baud rate, if required for the network .
Also change any additional addressing parameters
5 .
Press ‘S’ to save the BACnet configuration settings.
6 .
Verify “Flash write – success” is shown for configuration
pages 1 and 2 . Otherwise, save the settings again .
Figure 1:
BACnet Configuration Menu
Daikin Applied - MT2300_WSHP_Ser2
BACnet FW HP4 v2.0 UnitApp HP4 BB=v2.0,IO=v2.0
============== SW PN 2507443 ===================
DEVICE
1) Instance .......... 3101127
2) Name .............. MT2300_WSHP_Ser2_3101127
3) Location ...........
4) Description ........
5) Units ..............English
MS/TP
6) Baudrate ...........38400
7) MaxMasters .........127
M) MAC Address ..... 127
TERMINAL
8) EIA-232 Baudrate ... 19200
B) Backup Configuration
R) Restore Configuration
S) Save settings
--------------------------------------------