Daikin MICROTECH SMARTSOURCE 2300 WSHP Скачать руководство пользователя страница 16

BACNET DATA TABLES

MT2300 WSHP BACNET INTEGRATION

DAIKIN  APPLIED

16 

Table 5: Binary Inputs, Continued

Point Name

Object 

Type/

Instance

BACnet Object 

Name

Range

Description

Compressor Dual Speed 

Option

(SmartSource Series2)  

BI:34

IO_ConfigSw10

0 = Off  

1 = On

Indicates the compressor type configured for the unit. Applies to SmartSource 

Series2 application .  

0 = Off: Single speed compressor  

1 = On: Dual speed compressor

Lead Compressor Select 

Option

 (SmartSource SS2C) 

Indicates the lead compressor selection configured for the unit. Applies to  

SmartSource SS2C application . 

0 = Off: Compressor 1 is lead  

1 = On: Compressor 2 is lead

Humidistat Input

BI:35

Humidistat

0 = Inactive

1 = Active

Indicates the status of the humidistat signal . The thermsostat uses this input 

when dehumidification or waterside economizer is required. The network variable 

(MSV:16) overrides the humidistat input . 

This switch is effective only when the network scheduling is not in use.

Table 6: Binary Outputs

Point Name

Object 

Type/

Instance

BACnet Object 

Name

Read/

Write 

Access

Description

Thermostat Alarm

BO:1

Alarm

R

Thermostat alarm output status .

0 = Alarm output command is Off (0 VAC)

1 = Alarm output command is On (24 VAC)

Compressor 1 

BO:2

Comp1Out

R

Compressor 1 output command status .

0 = Compressor 1 command is Off  

1 = Compressor 1 command is On  

Fan Main Enable

BO:3

FanMainOut

R

Fan main enable output command status .

0 = 

Fan main command is Off

1 = Fan main command is On

Fan Speed

BO:4

FanLowOut

R

Fan speed output command status . Applies only when the Fan Main output command 

is On .
0 = Fan high speed command is On

1 = Fan low speed command is On

Pump Request

BO:5

PumpOut

R

Pump output command status for loop fluid flow.
0 = Pump command is Off

1 = Pump command is On

Reversing Valve 1

BO:6

RevVlv1Out

R

Compressor 1 reversing valve output command status .

0 = Reversing valve 1 command is Off (cooling)

1 = Reversing valve 1 command is On (heating)

Compressor 2 / Compressor 

High Capacity

BO:7

Comp2Out

R

Compressor 2 output command status .

0 = Compressor 2 command is Off  

1 = Compressor 2 command is On  

Reversing Valve 2

BO:8

RevVlv2Out

R

Compressor 2 reversing valve output command status .

0 = Reversing valve 2 command is Off (cooling)

1 = Reversing valve 2 command is On (heating)

Auxiliary Heat 1

BO:9

AuxHeat1Out

R

Auxiliary heat 1 output command status. Applies when unit is configured to use 

supplemental electric heat, boilerless electric heat, or hydronic heating . 

0 = Electric heat 1 command is Off  

1 = Electric heat 1 command is On  

Auxiliary Heat 2

BO:10

AuxHeat2Out

R

Auxiliary heat 2 output command status. Applies when unit is configured to use 

supplemental electric heat or boilerless electric heat . 

0 = Electric heat 2 command is Off  

1 = Electric heat 2 command is On  

Hot Gas Reheat

BO:11

HGR_Out

R

Hot gas reheat (HGR) output command status .

0 = HGR command is Off (valve is closed)

1 = HGR command is On (valve is open)

Waterside Economizer

BO:12

WSE_Out

R

Waterside economizer (WSE) output command status .

0 = WSE command is Off (valve is closed)

1 = WSE command is On (valve is open)

Содержание MICROTECH SMARTSOURCE 2300 WSHP

Страница 1: ...00 WSHP UNIT CONTROLLER MODELS SCH SDH SMH SNH AND SSH STH WITH R32 REFRIGERANT SCH SDH SMH SNH AND SSH STH LEARN MORE AT DAIKINAPPLIED COM MICROTECH SMARTSOURCE WSHP BACNET NETWORK INTEGRATION GUIDE...

Страница 2: ...pported 26 Device Management 26 Segmentation Capability 26 Data Link Layer Options 26 Device Address Binding 26 Character Sets Supported 26 Standard Object Types Supported 27 Revision History 28 2024...

Страница 3: ...Controller Operation Manual OM 1364 Daikin Applied www DaikinApplied com MicroTech SmartSource BACnet Communication Module Installation Manual IM 1363 Daikin Applied www DaikinApplied com BACnet A Da...

Страница 4: ...ng Vendor Identifier 120 3 Unsigned 16 Model Name 70 SmartSource Series2 MT2300_WSHP_Ser2 Character String SmartSource SS2C MT2300_WSHP_SS2C Firmware Revision 44 SmartSource Series2 HP4 v2 0 Character...

Страница 5: ...u Figure 1 The BACnet configuration menu is accessed using a serial application like Windows HyperTerminal or PuTTY It is assumed that the user is familiar with such an application Addressing must be...

Страница 6: ...ter to the BACnet communication module 3 Once connected press the Enter key to display the menu shown in Figure 1 4 Use the BACnet configuration menu to change the terminal EIA 232 baud rate if requir...

Страница 7: ...is requested then the communication module s non volatile memory is set to default values A cold reset can also be performed by the following button sequence on the BACnet communication module 1 Pres...

Страница 8: ...ischarge air temperature sensor value if installed and configured with a valid input 3 Local Setpoint Adjust AI 5 LocalSetpt 55 to 95 F 12 78 to 35 C Default 32 F 0 C R N Reflects the value of the sel...

Страница 9: ...disables this feature Interstage OFF Timer AV 8 cpIntStgOffTmr 0 to 1200 sec Default 0 W Y A countdown timer that defines the minimum period of time between turn off of the subsequent heating and cool...

Страница 10: ...r reboot Network Temperature Setpoint AV 19 NetworkSetpoint 50 to 95 F 10 to 35 C Default6 621 806 F 327 67 C C N Allows the network to set the reference setpoint in occupied and standby occupancy mod...

Страница 11: ...lt 28 F 2 22 C W Y Value of the low entering water temperature EWT setpoint when using a glycol loop fluid Low EWT Setpoint for Water AV 31 cpLowEwtSptWtr 40 to 65 F 4 44 to 18 34 C Default 55 F 12 78...

Страница 12: ...the isolation valve output energizes allowing the supply water flow timer to expire Local Space Dewpoint AV 50 LocalDewpointCalc 32 to 150 F 0 to 65 55 C Default Null6 R N Reflects the local space de...

Страница 13: ...ystemMinInstance the Present Value is writeable and it has a default value of 3101000 During the commissioning process the present value of AV412 is added to the MAC Address to determine the Device In...

Страница 14: ...rst stage cooling 1 Active Thermostat switch is closed indicating first stage cooling is active Thermostat Cooling Stage 2 BI 9 Tstat_Y2 0 Inactive 1 Active Thermostat input for cooling Applies when u...

Страница 15: ...esent 1 On I O expansion module is required Compressor Availability SmartSource SS2C BI 21 BB_ConfigSw7 0 Off 1 On Configuration switches 7 and 8 settings for compressor availabillity Applies to Smart...

Страница 16: ...Fan main command is On Fan Speed BO 4 FanLowOut R Fan speed output command status Applies only when the Fan Main output command is On 0 Fan high speed command is On 1 Fan low speed command is On Pump...

Страница 17: ...ensor input or space dewpoint Fan Run Status MSI 5 FanRunStatus 1 Fan is Off 2 Fan is On R N Commanded fan run status Used in conjunction with fan speed command AV 38 to indicate fan speed status Para...

Страница 18: ...tion mode Auto Off Heat Cool Dehumidification or Fan Only Application Mode does not force the unit into any state However it does disable certain unit operations Examples 1 Application Mode of Cool di...

Страница 19: ...teable C Commandable Table 10 Device Object Properties Point Name Object Type Instance BACnet Object Name Range Default in Units Read Write Access2 Non volatile Memory1 Description Description Device...

Страница 20: ...n alarm is cleared but the alarm condition still exists the controller immediately re activates the alarm NOTE Cycling power to the unit controller resets the fault alarm Intelligent Alarm Reset The M...

Страница 21: ...sure 27 Cmp1 Hi Disch Temp Compressor 1 High Discharge Temperature Manual Yes Compressor high and low pressure switches have both opened simultaneously indicating a compressor high discharge temperatu...

Страница 22: ...y 26 WSE Low Temp Cutout Waterside Economizer Low Temperature Cutout Auto No Alarm indicates a low EWT condition Applies to units that have a waterside economizer with an active request for cooling 1...

Страница 23: ...ion parameters Table 13 Occupancy Parameters Parameter Description EffectOccup MSV 6 Indicates the actual occupancy mode of the unit Occupied Unoccupied Bypass Standby OccManCmd MSV 7 Network occupanc...

Страница 24: ...ffective Heat ON SP 60 F AV35 0 5 F Deadband Factor 75 70 2 2 5 Effective Cool ON SP 77 3 80 F Effective Heat OFF SP 60 2 62 F Reference SP 72 0 5 72 5 F Effective Cool ON SP 72 5 2 5 75 F Effective C...

Страница 25: ...P EffCoolOnSP AV10 EffHeatOnSP AV4 AV24 EffHeatOffSP EffHeatOnSP AV10 5 The unit is operating in Standby mode with Short Range Local Setpoint Adjust selected and MSV14 2 EffCoolOnSP HP1 AV2 AV25 EffCo...

Страница 26: ...BACnet Smart Sensor B SS BACnet Smart Actuator B SA BACnet Interoperability Building Blocks Supported Data Sharing Data Sharing Read Property B DS RP B Data Sharing Read Property Multiple B DS RPM B...

Страница 27: ...COV_Increment Present_Value Priority_Array Relinquish_Default Binary Input Active_Text Description Inactive_Text Binary Value Active_Text Description Inactive_Text Present_Value Multi state Input Sta...

Страница 28: ...and WSHP single two stage and dual compressor applications including the following Added analog value network points for monitoring and control of relative humidity Added analog value network points f...

Страница 29: ...S COILS CONDENSING UN I T S A IR HANDLERS WATER COOLED CHILLERS AIR COOLED CHI L L ER S MOD U LAR CENTRAL PLANTS SITELINE BUILDING CONTROL S UNIT HEATERS FAN COILS AIR PURIFIERS WATER SOURCE HEAT PUMP...

Страница 30: ...ANDLERS WATER COOLED CHILLERS AIR COOLED CHI L L ER S MOD U LAR CENTRAL PLANTS SITELINE BUILDING CONTROL S UNIT HEATERS FAN COILS AIR PURIFIERS WATER SOURCE HEAT PUMPS VARIABLE AIR VOLUME UNITS UNIT V...

Отзывы: