ALARMS

MT2300 WSHP BACNET INTEGRATION

DAIKIN  APPLIED

22 

Table 11. BACnet Alarms by Priority, Continued

Alarm 

Enumeration

Alarm Text

Description

Clear

Network 

Reset

Details

3

20

EWT Snsr Flt

Entering Water Temperature 

(EWT) Sensor Fault

Manual

Yes

The entering water temperature (EWT) sensor input 

vaue exceeds the allowable temperature range . 

Applies to boilerless electric heat and hydronic 

heating/cooling unit configurations only.

21

Room Snsr Flt

Room  Temperature  Sensor  Fault       

Manual

Yes

The space temperature sensor input vaue exceeds 

the allowable temperature range . 

22

RAT Snsr Flt

Return Air Temperature (RAT) 

Sensor Fault                     

Manual

Yes

The return air temperature sensor input vaue 

exceeds the allowable temperature range . Applies 

to units with control temperature enabled or with 

hot gas reheat (HGR) 

23

RH Snsr Flt

Space Relative Humidity (RH) 

Sensor Fault

Manual

Yes

The relative humidity sensor input vaue exceeds 

the allowable range . 

24

EWT Low

Entering Water Temperature 

(EWT) Low                    

Auto

No

Alarm indicates that the EWT is below the selected 

water or glycol setpoint .  Applies to units in heating 

without boilerless electric heat .

25

 Condensate Overflow

Condensate Overflow     

Auto

Yes

Alarm indicates the detection of water in the 

condensate overflow pan for 60 consecutive 

seconds . Alarm disables cooling and 

dehumidification operation until drain pan is dry.

26

 WSE Low Temp Cutout

Waterside Economizer Low 

Temperature Cutout

Auto

No

Alarm indicates a low EWT condition . Applies to 

units that have a waterside economizer with an 

active request for cooling .

1

 The intelligent reset feature automatically clears an alarm the first two times it occurs within 24 hours. The third time the alarm occurs within this time, the alarm 

requires a manual reset .  

For WSHP applications where the refrigerant charge limits need to meet UL60335-2-40 standard requirements of Title 24, the MicroTech controller is supplied with 

an additional A2L leak detection mitigation board and alarm support .

An Invalid Configuration alarm can occur for these reasons: 1. An application software mismatch between the baseboard and IO expansion module due to invalid 

configuration switch 9 settings. 2. A hardware error due to the installation of an internal test application. 3. Series2 application only: The baseboard detects an 

IO expansion module but its configuration switch 8 is incorrectly set to the OFF position. The following (4-7) apply to SS2C application only: 4. The baseboard 

configuration switch 10 is incorrectly set to the ON position, indicating an invalid dual speed fan selection. 5. The baseboard configuration switches 7 and 8 are 

incorrectly set to the ON position, indicating an invalid compressor selection . 6 . The IO expansion module is enabling HGR but the baseboard has no compressors 

available on the 7 and 8 configuration switches. 7. No compressors are available, and no form of heating and cooling options are selected.

Содержание MICROTECH SMARTSOURCE 2300 WSHP

Страница 1: ...00 WSHP UNIT CONTROLLER MODELS SCH SDH SMH SNH AND SSH STH WITH R32 REFRIGERANT SCH SDH SMH SNH AND SSH STH LEARN MORE AT DAIKINAPPLIED COM MICROTECH SMARTSOURCE WSHP BACNET NETWORK INTEGRATION GUIDE...

Страница 2: ...pported 26 Device Management 26 Segmentation Capability 26 Data Link Layer Options 26 Device Address Binding 26 Character Sets Supported 26 Standard Object Types Supported 27 Revision History 28 2024...

Страница 3: ...Controller Operation Manual OM 1364 Daikin Applied www DaikinApplied com MicroTech SmartSource BACnet Communication Module Installation Manual IM 1363 Daikin Applied www DaikinApplied com BACnet A Da...

Страница 4: ...ng Vendor Identifier 120 3 Unsigned 16 Model Name 70 SmartSource Series2 MT2300_WSHP_Ser2 Character String SmartSource SS2C MT2300_WSHP_SS2C Firmware Revision 44 SmartSource Series2 HP4 v2 0 Character...

Страница 5: ...u Figure 1 The BACnet configuration menu is accessed using a serial application like Windows HyperTerminal or PuTTY It is assumed that the user is familiar with such an application Addressing must be...

Страница 6: ...ter to the BACnet communication module 3 Once connected press the Enter key to display the menu shown in Figure 1 4 Use the BACnet configuration menu to change the terminal EIA 232 baud rate if requir...

Страница 7: ...is requested then the communication module s non volatile memory is set to default values A cold reset can also be performed by the following button sequence on the BACnet communication module 1 Pres...

Страница 8: ...ischarge air temperature sensor value if installed and configured with a valid input 3 Local Setpoint Adjust AI 5 LocalSetpt 55 to 95 F 12 78 to 35 C Default 32 F 0 C R N Reflects the value of the sel...

Страница 9: ...disables this feature Interstage OFF Timer AV 8 cpIntStgOffTmr 0 to 1200 sec Default 0 W Y A countdown timer that defines the minimum period of time between turn off of the subsequent heating and cool...

Страница 10: ...r reboot Network Temperature Setpoint AV 19 NetworkSetpoint 50 to 95 F 10 to 35 C Default6 621 806 F 327 67 C C N Allows the network to set the reference setpoint in occupied and standby occupancy mod...

Страница 11: ...lt 28 F 2 22 C W Y Value of the low entering water temperature EWT setpoint when using a glycol loop fluid Low EWT Setpoint for Water AV 31 cpLowEwtSptWtr 40 to 65 F 4 44 to 18 34 C Default 55 F 12 78...

Страница 12: ...the isolation valve output energizes allowing the supply water flow timer to expire Local Space Dewpoint AV 50 LocalDewpointCalc 32 to 150 F 0 to 65 55 C Default Null6 R N Reflects the local space de...

Страница 13: ...ystemMinInstance the Present Value is writeable and it has a default value of 3101000 During the commissioning process the present value of AV412 is added to the MAC Address to determine the Device In...

Страница 14: ...rst stage cooling 1 Active Thermostat switch is closed indicating first stage cooling is active Thermostat Cooling Stage 2 BI 9 Tstat_Y2 0 Inactive 1 Active Thermostat input for cooling Applies when u...

Страница 15: ...esent 1 On I O expansion module is required Compressor Availability SmartSource SS2C BI 21 BB_ConfigSw7 0 Off 1 On Configuration switches 7 and 8 settings for compressor availabillity Applies to Smart...

Страница 16: ...Fan main command is On Fan Speed BO 4 FanLowOut R Fan speed output command status Applies only when the Fan Main output command is On 0 Fan high speed command is On 1 Fan low speed command is On Pump...

Страница 17: ...ensor input or space dewpoint Fan Run Status MSI 5 FanRunStatus 1 Fan is Off 2 Fan is On R N Commanded fan run status Used in conjunction with fan speed command AV 38 to indicate fan speed status Para...

Страница 18: ...tion mode Auto Off Heat Cool Dehumidification or Fan Only Application Mode does not force the unit into any state However it does disable certain unit operations Examples 1 Application Mode of Cool di...

Страница 19: ...teable C Commandable Table 10 Device Object Properties Point Name Object Type Instance BACnet Object Name Range Default in Units Read Write Access2 Non volatile Memory1 Description Description Device...

Страница 20: ...n alarm is cleared but the alarm condition still exists the controller immediately re activates the alarm NOTE Cycling power to the unit controller resets the fault alarm Intelligent Alarm Reset The M...

Страница 21: ...sure 27 Cmp1 Hi Disch Temp Compressor 1 High Discharge Temperature Manual Yes Compressor high and low pressure switches have both opened simultaneously indicating a compressor high discharge temperatu...

Страница 22: ...y 26 WSE Low Temp Cutout Waterside Economizer Low Temperature Cutout Auto No Alarm indicates a low EWT condition Applies to units that have a waterside economizer with an active request for cooling 1...

Страница 23: ...ion parameters Table 13 Occupancy Parameters Parameter Description EffectOccup MSV 6 Indicates the actual occupancy mode of the unit Occupied Unoccupied Bypass Standby OccManCmd MSV 7 Network occupanc...

Страница 24: ...ffective Heat ON SP 60 F AV35 0 5 F Deadband Factor 75 70 2 2 5 Effective Cool ON SP 77 3 80 F Effective Heat OFF SP 60 2 62 F Reference SP 72 0 5 72 5 F Effective Cool ON SP 72 5 2 5 75 F Effective C...

Страница 25: ...P EffCoolOnSP AV10 EffHeatOnSP AV4 AV24 EffHeatOffSP EffHeatOnSP AV10 5 The unit is operating in Standby mode with Short Range Local Setpoint Adjust selected and MSV14 2 EffCoolOnSP HP1 AV2 AV25 EffCo...

Страница 26: ...BACnet Smart Sensor B SS BACnet Smart Actuator B SA BACnet Interoperability Building Blocks Supported Data Sharing Data Sharing Read Property B DS RP B Data Sharing Read Property Multiple B DS RPM B...

Страница 27: ...COV_Increment Present_Value Priority_Array Relinquish_Default Binary Input Active_Text Description Inactive_Text Binary Value Active_Text Description Inactive_Text Present_Value Multi state Input Sta...

Страница 28: ...and WSHP single two stage and dual compressor applications including the following Added analog value network points for monitoring and control of relative humidity Added analog value network points f...

Страница 29: ...S COILS CONDENSING UN I T S A IR HANDLERS WATER COOLED CHILLERS AIR COOLED CHI L L ER S MOD U LAR CENTRAL PLANTS SITELINE BUILDING CONTROL S UNIT HEATERS FAN COILS AIR PURIFIERS WATER SOURCE HEAT PUMP...

Страница 30: ...ANDLERS WATER COOLED CHILLERS AIR COOLED CHI L L ER S MOD U LAR CENTRAL PLANTS SITELINE BUILDING CONTROL S UNIT HEATERS FAN COILS AIR PURIFIERS WATER SOURCE HEAT PUMPS VARIABLE AIR VOLUME UNITS UNIT V...

Отзывы: