BACNET DATA TABLES

MT2300 WSHP BACNET INTEGRATION

DAIKIN  APPLIED

18 

Table 9: Multi-State Values, Continued

Point Name

Object 

Type/

Instance

BACnet Object 

Name

Range/Default 

 

(in Units)

Read/

Write 

Access

2

Non-

volatile 

Memory

1

Description

Effective Occupancy

MSV:6

EffectOccup

1 = Occupied

2 = Unoccupied

3 = Bypass

4 = Standby

5 = Null

R

N

Indicates the unit’s current occupancy mode .  

The mode tin which the unit operates depends 

on Occupancy Schedule, Occupancy Schedule 

Override, and/or an Occupancy Sensor. Reflects the 

local unoccupied input unless the MSV:7, MSV:8, or 

MSV:9 network overrides are not in a Null state . See 

Effective Occupancy Modes

 .

Occupancy Override 

Input

MSV:7

OccManCmd

1 = Occupied

2 = Unoccupied

3 = Bypass

4 = Standby

5 = Null

Default: 5 = Null

C

N

Network command to override the Occupancy 

Schedule .  Occupancy Schedule Override has 

priority over the Occupancy Schedule and Remote 

Occupancy Sensor .  It also monitors the Local Timed 

Override hardwired input that places the unit in the 

Occupied mode during the amount of time declared 

in Timed Override Setpoint .  Schedule Override 

and/or an Occupancy Sensor . The network override 

reverts back to its default value upon unit controller 

reboot . See 

Effective Occupancy Modes

 .

Occupancy Scheduler

MSV:8

OccSchedule

1 = Occupied

2 = Unoccupied

3 = Standby

4 = Null

Default: 4 = Null

C

N

Commands the WSHP into different occupancy 

modes .  A scheduler or a supervisory controller 

typically sends the command using Schedule 

Override .

3

 The network override reverts back to 

its default value upon unit controller reboot . See 

Effective Occupancy Modes

 .

Occupancy Sensor 

MSV:9

OccSensor

1 = Occupied

2 = Unoccupied

3 = Null

Default: 3 = Null

C

N

Network input that indicates the presence of 

occupants in the space (motion detection) .

7

 The 

network override will revert back to its default value 

upon unit controller reboot . See 

Effective Occupancy 

Modes

 .

Application Mode

MSV:10

ApplicMode

1 = Auto

2 = Heat

3 = Cool

4 = Off

5 = Fan Only

6 = Dehumid

7 = Null

Default: 7 = Null

C

N

Sets the unit in an application mode (Auto, Off, 

Heat, Cool, Dehumidification, or Fan Only). 

Application Mode does not “force” the unit into 

any state .  However, it does disable certain unit 

operations . Examples: 1) Application Mode of Cool 

disables heating, 2) Heat disables cooling and 

dehumidification, and 3) Fan Only disables heating, 

cooling, and dehumidification.

7

 MSV:10 overrides 

the local room sensor’s System Mode Switch (Heat/

Cool/Auto) . The local System Mode Switch is only 

used when MSV:10 is set to 7 (Null) . 
The network override reverts back to its default value 

upon unit controller reboot .

Auxiliary Heat Enable

MSV:11

AuxHeatEnable

1 = Disabled

2 = Enabled

3 = Null

Default: 3 = Null

C

N

Enables or disables auxiliary heat for units with 

electric heat . Electric heat is always enabled when 

it is the only source of heating, and is unaffected by 

this variable .  The default state is Null, in which case 

auxiliary heat is enabled .

  

The network override reverts back to its default value 

upon unit controller reboot .

Energy Hold Off

MSV:12

EnergyHoldOff

1 = Normal

2 = Energy Hold Off

3 = Null

Default: 3 = Null

C

N

When the unit is in the Energy Hold Off mode, the 

unit uses Standby setpoints . This command has 

priority over Effective Occupancy. The network 

override reverts back to its default value upon unit 

controller reboot .

Pump Request Output

MSV:13

PumpRequest

1 = No Request for Flow

2 = Request for Flow

3 = Null

Default: 3 = Null

R

N

Indicates when the unit is requesting flow from 

the loop water controller .  The loop pump must be 

running to provide adequate flow through the unit so 

the compressor(s) can operate safely .  Allows the 

network to access whether proper loop fluid flow is 

occurring .

Room Sensor 

Setpoint Adjust 

Enable/Disable

MSV:14

cpLocSpEnable

1 = Disabled

2 = Enabled

Default: 2 = Enabled

W

Y

Enables or disables the local hardwired setpoint 

adjustment . If the value of MSV:14 is set to 1, this 

disables the setpoint control from a room sensor and 

enables the setpoint control from the network .

Units 

(English/Metric)

MSV:15

Units

1 = English (E)

2 = Metric (M)

Default: 1= English 

W

Y

Units of measure for temperature conversion . 

Switching the default of English to Metric changes 

the temperature values for all applicable properties in 

the BACnet application . 

Содержание MICROTECH SMARTSOURCE 2300 WSHP

Страница 1: ...00 WSHP UNIT CONTROLLER MODELS SCH SDH SMH SNH AND SSH STH WITH R32 REFRIGERANT SCH SDH SMH SNH AND SSH STH LEARN MORE AT DAIKINAPPLIED COM MICROTECH SMARTSOURCE WSHP BACNET NETWORK INTEGRATION GUIDE...

Страница 2: ...pported 26 Device Management 26 Segmentation Capability 26 Data Link Layer Options 26 Device Address Binding 26 Character Sets Supported 26 Standard Object Types Supported 27 Revision History 28 2024...

Страница 3: ...Controller Operation Manual OM 1364 Daikin Applied www DaikinApplied com MicroTech SmartSource BACnet Communication Module Installation Manual IM 1363 Daikin Applied www DaikinApplied com BACnet A Da...

Страница 4: ...ng Vendor Identifier 120 3 Unsigned 16 Model Name 70 SmartSource Series2 MT2300_WSHP_Ser2 Character String SmartSource SS2C MT2300_WSHP_SS2C Firmware Revision 44 SmartSource Series2 HP4 v2 0 Character...

Страница 5: ...u Figure 1 The BACnet configuration menu is accessed using a serial application like Windows HyperTerminal or PuTTY It is assumed that the user is familiar with such an application Addressing must be...

Страница 6: ...ter to the BACnet communication module 3 Once connected press the Enter key to display the menu shown in Figure 1 4 Use the BACnet configuration menu to change the terminal EIA 232 baud rate if requir...

Страница 7: ...is requested then the communication module s non volatile memory is set to default values A cold reset can also be performed by the following button sequence on the BACnet communication module 1 Pres...

Страница 8: ...ischarge air temperature sensor value if installed and configured with a valid input 3 Local Setpoint Adjust AI 5 LocalSetpt 55 to 95 F 12 78 to 35 C Default 32 F 0 C R N Reflects the value of the sel...

Страница 9: ...disables this feature Interstage OFF Timer AV 8 cpIntStgOffTmr 0 to 1200 sec Default 0 W Y A countdown timer that defines the minimum period of time between turn off of the subsequent heating and cool...

Страница 10: ...r reboot Network Temperature Setpoint AV 19 NetworkSetpoint 50 to 95 F 10 to 35 C Default6 621 806 F 327 67 C C N Allows the network to set the reference setpoint in occupied and standby occupancy mod...

Страница 11: ...lt 28 F 2 22 C W Y Value of the low entering water temperature EWT setpoint when using a glycol loop fluid Low EWT Setpoint for Water AV 31 cpLowEwtSptWtr 40 to 65 F 4 44 to 18 34 C Default 55 F 12 78...

Страница 12: ...the isolation valve output energizes allowing the supply water flow timer to expire Local Space Dewpoint AV 50 LocalDewpointCalc 32 to 150 F 0 to 65 55 C Default Null6 R N Reflects the local space de...

Страница 13: ...ystemMinInstance the Present Value is writeable and it has a default value of 3101000 During the commissioning process the present value of AV412 is added to the MAC Address to determine the Device In...

Страница 14: ...rst stage cooling 1 Active Thermostat switch is closed indicating first stage cooling is active Thermostat Cooling Stage 2 BI 9 Tstat_Y2 0 Inactive 1 Active Thermostat input for cooling Applies when u...

Страница 15: ...esent 1 On I O expansion module is required Compressor Availability SmartSource SS2C BI 21 BB_ConfigSw7 0 Off 1 On Configuration switches 7 and 8 settings for compressor availabillity Applies to Smart...

Страница 16: ...Fan main command is On Fan Speed BO 4 FanLowOut R Fan speed output command status Applies only when the Fan Main output command is On 0 Fan high speed command is On 1 Fan low speed command is On Pump...

Страница 17: ...ensor input or space dewpoint Fan Run Status MSI 5 FanRunStatus 1 Fan is Off 2 Fan is On R N Commanded fan run status Used in conjunction with fan speed command AV 38 to indicate fan speed status Para...

Страница 18: ...tion mode Auto Off Heat Cool Dehumidification or Fan Only Application Mode does not force the unit into any state However it does disable certain unit operations Examples 1 Application Mode of Cool di...

Страница 19: ...teable C Commandable Table 10 Device Object Properties Point Name Object Type Instance BACnet Object Name Range Default in Units Read Write Access2 Non volatile Memory1 Description Description Device...

Страница 20: ...n alarm is cleared but the alarm condition still exists the controller immediately re activates the alarm NOTE Cycling power to the unit controller resets the fault alarm Intelligent Alarm Reset The M...

Страница 21: ...sure 27 Cmp1 Hi Disch Temp Compressor 1 High Discharge Temperature Manual Yes Compressor high and low pressure switches have both opened simultaneously indicating a compressor high discharge temperatu...

Страница 22: ...y 26 WSE Low Temp Cutout Waterside Economizer Low Temperature Cutout Auto No Alarm indicates a low EWT condition Applies to units that have a waterside economizer with an active request for cooling 1...

Страница 23: ...ion parameters Table 13 Occupancy Parameters Parameter Description EffectOccup MSV 6 Indicates the actual occupancy mode of the unit Occupied Unoccupied Bypass Standby OccManCmd MSV 7 Network occupanc...

Страница 24: ...ffective Heat ON SP 60 F AV35 0 5 F Deadband Factor 75 70 2 2 5 Effective Cool ON SP 77 3 80 F Effective Heat OFF SP 60 2 62 F Reference SP 72 0 5 72 5 F Effective Cool ON SP 72 5 2 5 75 F Effective C...

Страница 25: ...P EffCoolOnSP AV10 EffHeatOnSP AV4 AV24 EffHeatOffSP EffHeatOnSP AV10 5 The unit is operating in Standby mode with Short Range Local Setpoint Adjust selected and MSV14 2 EffCoolOnSP HP1 AV2 AV25 EffCo...

Страница 26: ...BACnet Smart Sensor B SS BACnet Smart Actuator B SA BACnet Interoperability Building Blocks Supported Data Sharing Data Sharing Read Property B DS RP B Data Sharing Read Property Multiple B DS RPM B...

Страница 27: ...COV_Increment Present_Value Priority_Array Relinquish_Default Binary Input Active_Text Description Inactive_Text Binary Value Active_Text Description Inactive_Text Present_Value Multi state Input Sta...

Страница 28: ...and WSHP single two stage and dual compressor applications including the following Added analog value network points for monitoring and control of relative humidity Added analog value network points f...

Страница 29: ...S COILS CONDENSING UN I T S A IR HANDLERS WATER COOLED CHILLERS AIR COOLED CHI L L ER S MOD U LAR CENTRAL PLANTS SITELINE BUILDING CONTROL S UNIT HEATERS FAN COILS AIR PURIFIERS WATER SOURCE HEAT PUMP...

Страница 30: ...ANDLERS WATER COOLED CHILLERS AIR COOLED CHI L L ER S MOD U LAR CENTRAL PLANTS SITELINE BUILDING CONTROL S UNIT HEATERS FAN COILS AIR PURIFIERS WATER SOURCE HEAT PUMPS VARIABLE AIR VOLUME UNITS UNIT V...

Отзывы: