ALARMS

ED 19129-1

WWW.DAIKINAPPLIED.COM

21 

Table 11: BACnet Alarms by Priority    

Alarm 

Enumeration

Alarm Text

Description

Clear

Network 

Reset

Details

3

 

1

No Alms

No Alarms

2

IO Comm Fail

IO Expansion Module 

Communication Fail

Auto

No

The IO expansion module is not communicating 

with the unit controller (baseboard) .

3

Software Err

Incompatible Software

Requires Reboot

No

Incorrect software part number or version number .

4

CnfgErr

Invalid Configuration

Requires Reboot

No

In general, an alarm indicates one of several 

conditions related to the unit controller baseboard 

and IO expansion module configuration switch 

settings .

 

Details about these conditions are 

provided in the table footnotes .

3

5

A2L Leak

A2L Mitigation Board Refrigerant 

Leak 

Auto

No

The A2L mitigation board has detected a refrigerant 

concentration level that requires action . When 

alarm occurs, the unit enters a fan-only state and 

fans run on high speed until alarm is cleared . 

6

A2L No Pwr

A2L Mitigation Board No Power

Auto

No

The 12V input from the A2L mitigation board has 

been lost. When this occurs, the unit enters the off-

alarm state . All control outputs are disabled except 

for reversing valves .

7

Cmp Brownout

Compressor Low Voltage 

Brownout

Auto

Yes

The 24V power input supplied to the baseboard is 

less than 80% of the reference voltage (the voltage 

level required to safely run the compressors) . 

The alarm forces the unit into normal shutdown to 

protect from low line voltage conditions . The alarm 

automatically clears once the voltage input exceeds 

the 90% reference voltage threshold .

2

8

Cmp1 Hi Pres

Compressor 1 High Pressure

Manual

Yes

Compressor high pressure switch indicates a high 

pressure condition .  

9

Cmp2 Hi Pres

Compressor 2 High Pressure

10

Cmp1 Lo Pres

Compressor 1 Low Pressure

Manual

Yes

Compressor low pressure switch indicates a low 

pressure condition for longer than the alarm delay 

timer default (AV:34) .

11

Cmp2 Lo Pres

Compressor 2 Low Pressure

27

Cmp1 Hi Disch Temp

Compressor 1 High Discharge 

Temperature

Manual

Yes

Compressor high and low pressure switches 

have both opened simultaneously, indicating a 

compressor high discharge temperature condition 

exists .

28

 Cmp2 Hi Disch Temp

Compressor 2 High Discharge 

Temperature

12

 Cmp1 Sctn Tmp Snsr 

Flt

 Compressor 1 Suction 

Temperature Sensor Fault

Manual

Yes

The compressor suction temperature sensor 

exceeds the allowable temperature range .

13

 Cmp2 Sctn Tmp Snsr 

Flt

 Compressor 2 Suction 

Temperature Sensor Fault

14

 LWT Snsr Flt

Leaving Water Temperature (LWT) 

Sensor Fault

Manual

Yes

The unit is configured for freeze fault detection and 

the LWT sensor exceeds the allowable temperature 

range .

15

Freeze Flt

Freeze  Fault  Detect                                    

Manual

Yes

The freezestat indicates that the leaving water 

temperature is below the allowable

 

setpoint for 

adequate freeze protection . Applies to both water 

and glycol loop applications .

16

Cmp1 Lo Sctn

Compressor 1 Low Suction 

Temperature         

 Auto / Intel

1

See Description

Yes

If the unit is in cooling or dehumidification mode, 

alarm indicates that the compressor low suction 

temperature is below the fixed alarm setpoint of 

28°F (-2 .22°C) . If the unit is in heating mode, the 

compressor low suction temperature alarm is 

determined by the loop fluid setpoint. This setpoint 

is based on the configuration switch 3 setting:
Switch 3 is Off: Water loop setpoint (AV:12) is used.

Switch 3 is On: Glycol loop setpoint (AV:11) is used .
Alarm clears automatically when in cooling/

dehumidification modes. Alarm is cleared using 

Intelligent Reset

1

 when in heating mode .

17

Cmp2 Lo Sctn

Compressor 2 Low Suction 

Temperature 

18

A2L Snsr Flt

A2L Mitigation Board Refrigerant 

Sensor Fault

Auto

No

The A2L mitigation board has detected a fault with 

one or more of the refrigerant sensors . The unit 

controller continues to operate normally with the 

fan at constant high speed .

19

 Cntrl Temp Snsr Flt

Control Temperature Sensor Fault 

Manual

Yes

The space / return air temperature sensor(s) input 

value exceeds the allowabe temperature range . 

Alarm applies to units that are configured for room 

sensor control or with hot gas reheat (HGR) .

Содержание MICROTECH SMARTSOURCE 2300 WSHP

Страница 1: ...00 WSHP UNIT CONTROLLER MODELS SCH SDH SMH SNH AND SSH STH WITH R32 REFRIGERANT SCH SDH SMH SNH AND SSH STH LEARN MORE AT DAIKINAPPLIED COM MICROTECH SMARTSOURCE WSHP BACNET NETWORK INTEGRATION GUIDE...

Страница 2: ...pported 26 Device Management 26 Segmentation Capability 26 Data Link Layer Options 26 Device Address Binding 26 Character Sets Supported 26 Standard Object Types Supported 27 Revision History 28 2024...

Страница 3: ...Controller Operation Manual OM 1364 Daikin Applied www DaikinApplied com MicroTech SmartSource BACnet Communication Module Installation Manual IM 1363 Daikin Applied www DaikinApplied com BACnet A Da...

Страница 4: ...ng Vendor Identifier 120 3 Unsigned 16 Model Name 70 SmartSource Series2 MT2300_WSHP_Ser2 Character String SmartSource SS2C MT2300_WSHP_SS2C Firmware Revision 44 SmartSource Series2 HP4 v2 0 Character...

Страница 5: ...u Figure 1 The BACnet configuration menu is accessed using a serial application like Windows HyperTerminal or PuTTY It is assumed that the user is familiar with such an application Addressing must be...

Страница 6: ...ter to the BACnet communication module 3 Once connected press the Enter key to display the menu shown in Figure 1 4 Use the BACnet configuration menu to change the terminal EIA 232 baud rate if requir...

Страница 7: ...is requested then the communication module s non volatile memory is set to default values A cold reset can also be performed by the following button sequence on the BACnet communication module 1 Pres...

Страница 8: ...ischarge air temperature sensor value if installed and configured with a valid input 3 Local Setpoint Adjust AI 5 LocalSetpt 55 to 95 F 12 78 to 35 C Default 32 F 0 C R N Reflects the value of the sel...

Страница 9: ...disables this feature Interstage OFF Timer AV 8 cpIntStgOffTmr 0 to 1200 sec Default 0 W Y A countdown timer that defines the minimum period of time between turn off of the subsequent heating and cool...

Страница 10: ...r reboot Network Temperature Setpoint AV 19 NetworkSetpoint 50 to 95 F 10 to 35 C Default6 621 806 F 327 67 C C N Allows the network to set the reference setpoint in occupied and standby occupancy mod...

Страница 11: ...lt 28 F 2 22 C W Y Value of the low entering water temperature EWT setpoint when using a glycol loop fluid Low EWT Setpoint for Water AV 31 cpLowEwtSptWtr 40 to 65 F 4 44 to 18 34 C Default 55 F 12 78...

Страница 12: ...the isolation valve output energizes allowing the supply water flow timer to expire Local Space Dewpoint AV 50 LocalDewpointCalc 32 to 150 F 0 to 65 55 C Default Null6 R N Reflects the local space de...

Страница 13: ...ystemMinInstance the Present Value is writeable and it has a default value of 3101000 During the commissioning process the present value of AV412 is added to the MAC Address to determine the Device In...

Страница 14: ...rst stage cooling 1 Active Thermostat switch is closed indicating first stage cooling is active Thermostat Cooling Stage 2 BI 9 Tstat_Y2 0 Inactive 1 Active Thermostat input for cooling Applies when u...

Страница 15: ...esent 1 On I O expansion module is required Compressor Availability SmartSource SS2C BI 21 BB_ConfigSw7 0 Off 1 On Configuration switches 7 and 8 settings for compressor availabillity Applies to Smart...

Страница 16: ...Fan main command is On Fan Speed BO 4 FanLowOut R Fan speed output command status Applies only when the Fan Main output command is On 0 Fan high speed command is On 1 Fan low speed command is On Pump...

Страница 17: ...ensor input or space dewpoint Fan Run Status MSI 5 FanRunStatus 1 Fan is Off 2 Fan is On R N Commanded fan run status Used in conjunction with fan speed command AV 38 to indicate fan speed status Para...

Страница 18: ...tion mode Auto Off Heat Cool Dehumidification or Fan Only Application Mode does not force the unit into any state However it does disable certain unit operations Examples 1 Application Mode of Cool di...

Страница 19: ...teable C Commandable Table 10 Device Object Properties Point Name Object Type Instance BACnet Object Name Range Default in Units Read Write Access2 Non volatile Memory1 Description Description Device...

Страница 20: ...n alarm is cleared but the alarm condition still exists the controller immediately re activates the alarm NOTE Cycling power to the unit controller resets the fault alarm Intelligent Alarm Reset The M...

Страница 21: ...sure 27 Cmp1 Hi Disch Temp Compressor 1 High Discharge Temperature Manual Yes Compressor high and low pressure switches have both opened simultaneously indicating a compressor high discharge temperatu...

Страница 22: ...y 26 WSE Low Temp Cutout Waterside Economizer Low Temperature Cutout Auto No Alarm indicates a low EWT condition Applies to units that have a waterside economizer with an active request for cooling 1...

Страница 23: ...ion parameters Table 13 Occupancy Parameters Parameter Description EffectOccup MSV 6 Indicates the actual occupancy mode of the unit Occupied Unoccupied Bypass Standby OccManCmd MSV 7 Network occupanc...

Страница 24: ...ffective Heat ON SP 60 F AV35 0 5 F Deadband Factor 75 70 2 2 5 Effective Cool ON SP 77 3 80 F Effective Heat OFF SP 60 2 62 F Reference SP 72 0 5 72 5 F Effective Cool ON SP 72 5 2 5 75 F Effective C...

Страница 25: ...P EffCoolOnSP AV10 EffHeatOnSP AV4 AV24 EffHeatOffSP EffHeatOnSP AV10 5 The unit is operating in Standby mode with Short Range Local Setpoint Adjust selected and MSV14 2 EffCoolOnSP HP1 AV2 AV25 EffCo...

Страница 26: ...BACnet Smart Sensor B SS BACnet Smart Actuator B SA BACnet Interoperability Building Blocks Supported Data Sharing Data Sharing Read Property B DS RP B Data Sharing Read Property Multiple B DS RPM B...

Страница 27: ...COV_Increment Present_Value Priority_Array Relinquish_Default Binary Input Active_Text Description Inactive_Text Binary Value Active_Text Description Inactive_Text Present_Value Multi state Input Sta...

Страница 28: ...and WSHP single two stage and dual compressor applications including the following Added analog value network points for monitoring and control of relative humidity Added analog value network points f...

Страница 29: ...S COILS CONDENSING UN I T S A IR HANDLERS WATER COOLED CHILLERS AIR COOLED CHI L L ER S MOD U LAR CENTRAL PLANTS SITELINE BUILDING CONTROL S UNIT HEATERS FAN COILS AIR PURIFIERS WATER SOURCE HEAT PUMP...

Страница 30: ...ANDLERS WATER COOLED CHILLERS AIR COOLED CHI L L ER S MOD U LAR CENTRAL PLANTS SITELINE BUILDING CONTROL S UNIT HEATERS FAN COILS AIR PURIFIERS WATER SOURCE HEAT PUMPS VARIABLE AIR VOLUME UNITS UNIT V...

Отзывы: