BACNET PICS
MT2300 WSHP BACNET INTEGRATION
DAIKIN APPLIED
26
BACnet PICS
This section contains the Protocol Implementation
Conformance Statement (PICS) for the MT2300 SmartSource
WSHP Single Compressor (Series2) and SmartSource Two
Compressor (SS2C) Unit Controller models as required
by ANSI/ASHRAE Standard 135-2012, BACnet: A Data
Communication Protocol for Building Automation and Control
Networks .
Protocol Implementation
Conformance Statement
Date
November 2023
Vendor Name
Daikin Applied
Model Name
Series2:
MT2300_WSHP_Ser2
SS2C:
MT2300_WSHP_SS2C
Application Software
Version
Series2:
HP4 BB=v2 .0 IO=v2 .0
SS2C:
HP5 BB=v2 .0, IO=v2 .0
Firmware Version
Series2: HP4 v2 .0
SS2C: HP5 v2 .0
PN 2507443020
PN 2507443020
BACnet Protocol
Version / Revision
1 .14
1
1
Note that 1 .14 represents Version 1, Revision 14
Product Description
The MicroTech WSHP unit controller with optional BACnet
communication module is designed to operate the heat pump
unit and integrate it into a BACnet building automation system .
BACnet Standardized Device
Profile
BACnet Advanced Workstation
(B-AWS)
BACnet Operator Workstation
(B-OWS)
BACnet Operator Display
(B-OD)
BACnet Building Controller
(B-BC)
BACnet Advanced Application Controller
(B-AAC)
BACnet Application Specific Controller
(B-ASC)
BACnet Smart Sensor
(B-SS)
BACnet Smart Actuator
(B-SA)
BACnet Interoperability Building
Blocks Supported
Data Sharing
Data Sharing – Read Property – B
DS-RP-B
Data Sharing – Read Property Multiple – B
DS-RPM-B
Data Sharing – Write Property – B
DS-WP-B
Data Sharing – Write Property Multiple – B
DS-WPM-B
Data Sharing – COV – B (15 Maximum Objects
Supported)
DS-COV-B
Device Management
Device Management – Dynamic Device Binding – B
DM-DDB-B
Device Management – Dynamic Object Binding – B
DM-DOB-B
Device Management – Device Communication Control – B
DM-DCC-B
Device Management – Time Synchronization – B
DM-TS-B
Device Management – Reinitialize Device – B
DM-RD-B
Segmentation Capability
Able to transmit segmented
messages
Window size
1 for MS/TP
2 . .8 for IP
Able to receive segmented
messages
Window size
1 for MS/TP
2 . .8 for IP
Data Link Layer Options
BACnet IP, (Annex J)
-
BACnet IP, (Annex J), Foreign Device
-
ISO 8802-3, Ethernet (Clause 7)
-
ANSI/ATA 878 .1, 2 .5 Mb . ARCNET (Clause 8)
-
ANSI/ATA 878 .1, RS-485 ARCNET (Clause
8), baud rate(s)
-
MS/TP master (Clause 9), baud rate(s)
9600
19200
38400
76800
MS/TP slave (Clause 9), baud rate(s)
9600
19200
38400
76800
Point-To-Point, EIA 232 (Clause 10), baud
rate(s)
-
Point-To-Point, modem, (Clause 10), baud
rate(s)
-
Device Address Binding
Is static device binding supported?
Yes
No
Character Sets Supported
NOTE:
Support for multiple character sets does not imply
they can be supported simultaneously .
UTF-8
IBM / Microsoft DBCS
ISO 8859-1
ISO 10646 (UCS-2)
ISO 10646 (UCS-4)
JIS C 6226