Field Settings
SiBE061121_A
124
Trial Operation and Field Settings
4.2
Standby Electricity Saving
Outline
25/35 Class Only
This function turns OFF the power supply to the outdoor unit and sets the indoor unit into
standby electricity saving mode, thus reducing the power consumption of the air conditioner.
Detail
The standby electricity saving function is turned OFF before shipping. The following
procedure is required for turning ON the function.
1. Check that the main power supply is turned OFF. Turn OFF if it has not been turned OFF.
2. Remove the stop valve cover.
3. Disconnect the selective connector for standby electricity saving.
4. Turn ON the main power supply.
Caution
1. Before connecting or disconnecting the selective connector for standby electricity saving,
make sure that the main power supply is turned OFF.
2. For the RXG50K3V1B model, the selective connector for standby electricity saving is
required. Do not disconnect it.
1
2
3
1
2
3
(R13526)
Function OFF
Function ON
Selective connector