SiBE061121_A
Troubleshooting
Service Diagnosis
83
Troubleshooting
Check No.01
Refer to P.106
Check No.12
Refer to P.108
Check No.13
Refer to P.109
Check No.14
Refer to P.109
Note:
OL (Q1L) activating temperature: 120°C
OL (Q1L) recovery temperature: 95°C
(R18333)
Caution
YES
NG
∗
Discharge pipe thermistor
NO
OK
OK
NG
NG
OK
NG
OK
∗
Refrigerant shortage
∗
Water mixed
∗
Stop valve
Insert the thermistor in
position.
Replace the discharge pipe
thermistor.
Replace the outdoor
electronic expansion valve
or the coil.
Refer to the refrigerant line
check procedure.
Replace the outdoor unit
PCB.
Replace the four way valve
or the coil.
Replace the outdoor unit
PCB.
Discharge
pipe thermistor
disconnected?
Check No. 01
Check the thermistors.
Check No. 13
Check the four way
valve.
Check No. 14
Check the refrigerant
line.
Check No. 12
Check the outdoor electronic
expansion valve.
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
YES
NO
Disconnect the connector [S40]
from the PCB.
Disconnect the 2 terminals of
the OL (Q1L).
Resistance
∞
Resistance
∞
Nearly 0
Ω
Nearly 0
Ω
∗
Connector [S40]
∗
2 terminals of OL (Q1L)
Replace the OL (Q1L).
Replace the OL harness.
Connect the connectors
properly.
Connectors are
properly connected?
Check
the resistance
between the 2 terminals on
the connector
[S40].
Check the
resistance between the
2 terminals of the OL
(Q1L).
Содержание FVXG25K2V1B
Страница 11: ...SiBE061121_A List of Functions 1 Part 1 List of Functions 1 Functions 2...
Страница 14: ...SiBE061121_A 4 Specifications Part 2 Specifications 1 Specifications 5...
Страница 63: ...SiBE061121_A Remote Controller 53 Part 5 Remote Controller 1 FVXG25 35 50K2V1B 54...
Страница 127: ...SiBE061121_A Check Service Diagnosis 117 RXG50K2V1B RXG50K3V1B R16073 Power module Power module R16692...