Trial Operation and Field Settings
125
4.3
Facility Setting Jumper (cooling at low outdoor
temperature)
Outline
RXG50K3V1B only
This function is limited only for facilities (the target of air conditioning is equipment (such as
computer)). Never use it in a residence or office (the space where there is a human).
Detail
You can expand the operation range to –10°C by cutting jumper J6 on the outdoor unit PCB. If
the outdoor temperature falls to –18°C or lower, the operation stops. If the outdoor temperature
rises, the operation starts again.
Caution
1. If the outdoor unit is installed where the outdoor heat exchanger of the unit is exposed to
direct wind, provide a windbreak wall.
2. Intermittent noises may be produced by the indoor unit due to the outdoor fan turning on and
off when using facility settings.
3. Do not place humidifiers or other items which might raise the humidity in rooms where facility
settings are being used.
A humidifier might cause dew condensation from the indoor unit outlet vent.
4. Cutting jumper sets the indoor fan tap to the highest position.
Caution
Replace the PCB if you accidentally cut a wrong jumper.
Jumpers are necessary for electronic circuit. Improper operation may occur if you cut any of
them.
(R18276)
GND
Cut the jumper J6.
J5
J7
J8
J6
Содержание FVXG25K2V1B
Страница 11: ...SiBE061121_A List of Functions 1 Part 1 List of Functions 1 Functions 2...
Страница 14: ...SiBE061121_A 4 Specifications Part 2 Specifications 1 Specifications 5...
Страница 63: ...SiBE061121_A Remote Controller 53 Part 5 Remote Controller 1 FVXG25 35 50K2V1B 54...
Страница 127: ...SiBE061121_A Check Service Diagnosis 117 RXG50K2V1B RXG50K3V1B R16073 Power module Power module R16692...