SiBE061121_A
Control Specification
Function and Control
49
3.11 Outdoor Electronic Expansion Valve Control
Outline
The following items are included in the outdoor electronic expansion valve control.
Outdoor electronic expansion valve is fully closed.
1. Outdoor electronic expansion valve is fully closed when turning on the power.
2. Pressure equalizing control
Open Control
1. Outdoor electronic expansion valve control when starting operation
2. Outdoor electronic expansion valve control when the frequency changes
3. Outdoor electronic expansion valve control for defrosting
4. Outdoor electronic expansion valve control when the discharge pipe temperature is
abnormally high
5. Outdoor electronic expansion valve control when the discharge pipe thermistor is
disconnected
Feedback Control
Target discharge pipe temperature control
Detail
The followings are the examples of outdoor electronic expansion valve control which function in
each operation mode.
Cooling
−
h
−
−
−
−
−
−
−
−
h
−
h
−
−
−
−
−
−
h
−
−
−
−
−
−
−
−
−
h
h
−
−
h
h
h
h
h
h
h
h
h
−
−
−
h
−
−
−
−
−
−
−
−
h
−
Heating
−
h
−
−
−
−
−
−
−
−
h
−
h
−
−
−
−
−
−
h
−
−
−
−
−
−
−
−
−
h
h
−
−
h
h
h
h
−
−
−
−
−
−
−
−
−
−
h
h
−
−
−
−
−
−
−
−
h
h
h
h
h
h
−
h
: Holding Functions
— : No Functions
Starting control
Control when the frequency changes
Target discharge pipe temperature control
Control for disconnection of the discharge
pipe thermistor
High discharge pipe temperature control
Pressure equalizing control
Opening limit control
Starting control
Control when the frequency changes
Target discharge pipe temperature control
Control for disconnection of the discharge
pipe thermistor
High discharge pipe temperature control
Defrost control
Pressure equalizing control
Opening limit control
When the power turns on or when the compressor
stops
When the operation starts
When the frequency changes under starting control
During target discharge pipe temperature control
When the frequency changes under target discharge
pipe temperature control
When the disconnection of the discharge pipe
thermistor is ascertained
When the frequency changes under the control for
disconnection of the discharge pipe thermistor
Under defrost control
Содержание FVXG25K2V1B
Страница 11: ...SiBE061121_A List of Functions 1 Part 1 List of Functions 1 Functions 2...
Страница 14: ...SiBE061121_A 4 Specifications Part 2 Specifications 1 Specifications 5...
Страница 63: ...SiBE061121_A Remote Controller 53 Part 5 Remote Controller 1 FVXG25 35 50K2V1B 54...
Страница 127: ...SiBE061121_A Check Service Diagnosis 117 RXG50K2V1B RXG50K3V1B R16073 Power module Power module R16692...