SiBE28-804
Field Settings
Test Operation
103
Setting of refrigerant recovery mode
When a refrigerant recovery unit is connected on site to recover refrigerant, fully open the
expansion valve of the outdoor unit to help the recovery.
[Work procedure]
(1) Stop operation.
(2) Turn ON refrigerant recovery mode by performing the following steps.
(3) Connect a refrigerant recovery unit to perform refrigerant recovery. (For a refrigerant
recovery port, refer to the installation manual.)
(4) Upon completion of refrigerant recovery, turn OFF refrigerant recovery mode by taking the
following steps or turning OFF the power of outdoor unit.
∗
1: If you become unsure how many times you have pushed the button, push the MODE (BS1)
button once to return to "Setting mode 1" and start the operating procedure all over again.
1
: OFF
9
: BLINK
8
: ON
Operating procedure
H1P H2P H3P H4P H5P H6P H7P
Push and hold the MODE (BS1) button of "Setting mode 1" for 5 seconds
or more and set to "Setting mode 2."
8 1 1 1 1 1 1
Push the SET (BS2) button 28 times to set the LED display as shown in
the table on the right. (
∗
1)
8 1 8 8 8 1 1
Push the RETURN (BS3) button once. (Present settings are displayed.)
8 1 1 1 1 1 9
Push the SET (BS2) button once to set the LED display as shown in the
table on the right.
8 1 1 1 1 9 1
Push the RETURN (BS3) button once to make a decision.
8 1 1 1 1 8 1
When the RETURN (BS3) button is pushed once again, the electronic
expansion valve opens fully.
(For RZQ-KTLT, the solenoid valve also opens.)
8 1 1 1 1 1 1
Operating procedure
H1P H2P H3P H4P H5P H6P H7P
Push the SET (BS2) button 28 times to set the LED display as shown in
the table on the right. (
∗
1)
8 1 8 8 8 1 1
Push the RETURN (BS3) button once. (Present settings are displayed.)
8 1 1 1 1 9 1
Push the SET (BS2) button once to set the LED display as shown in the
table on the right.
8 1 1 1 1 1 9
Push the RETURN (BS3) button once to make a decision.
8 1 1 1 1 1 8
When the RETURN (BS3) button is pushed once again, the electronic
expansion valve fully opens.
(For RZQ-KTLT, the solenoid valve also closes.)
8 1 1 1 1 1 1
Содержание FHQ100BUV1B x 2
Страница 1: ...SiBE28 804 SkyAir RZQ71C7V1B RZQ100 140C7V1B RZQS71 100C7V1B RZQS125 140C7V1B R 410A Heat Pump 50Hz ...
Страница 13: ...SiBE28 804 2 ...
Страница 19: ...Model Name and Power Supply SiBE28 804 8 General Information ...
Страница 29: ...Specifications SiBE28 804 18 Specifications ...
Страница 33: ...Wired Remote Controller SiBE28 804 22 Remote Controller 1 2 Installation ...
Страница 34: ...SiBE28 804 Wired Remote Controller Remote Controller 23 ...
Страница 43: ...SiBE28 804 32 Functional Description 6 Outdoor Unit Fan Speed Control 81 6 1 Outdoor Unit Fan Speed Control 81 ...
Страница 93: ...Outdoor Unit Fan Speed Control SiBE28 804 82 Functional Description ...
Страница 131: ...Test Run and Operation Data SiBE28 804 120 Test Operation ...
Страница 251: ...Troubleshooting by Remote Controller Display LED Display SiBE28 804 240 Troubleshooting ...
Страница 277: ...PCB Layout SiBE28 804 266 Appendix ...
Страница 297: ...RZQ100 140C7 RZQS125 140C7V1B SiBE28 804 286 Removal Procedure ...
Страница 311: ...SiBE28 804 iv Index ...