SiBE28-804
Indoor Unit Functional Concept
Functional Description
55
2.3
Condensation Avoidance Control
FHQ71~125, FAQ71·100
In cooling and dry operation, the following control is carried out in order to prevent dew
condensation when the horizontal blade blows air downward.
[Start condition]
[Dew condensation prevention control]
Dry operation with horizontal air flow is carried out for one hour (*1).
Note
1. When there is any change to heating/fan modes, airflow direction and operation ON/OFF
state during dew condensation prevention control, this control is reset.
2. *1: For FAQ71, the air flow is 44 degrees downward from the horizontal direction.
&
• Horizontal blade is set to downward flow
• Cooling operation (compressor operation) continues for A minutes.
FHQ
FAQ
A
30 min.
20 min.
Содержание FHQ100BUV1B x 2
Страница 1: ...SiBE28 804 SkyAir RZQ71C7V1B RZQ100 140C7V1B RZQS71 100C7V1B RZQS125 140C7V1B R 410A Heat Pump 50Hz ...
Страница 13: ...SiBE28 804 2 ...
Страница 19: ...Model Name and Power Supply SiBE28 804 8 General Information ...
Страница 29: ...Specifications SiBE28 804 18 Specifications ...
Страница 33: ...Wired Remote Controller SiBE28 804 22 Remote Controller 1 2 Installation ...
Страница 34: ...SiBE28 804 Wired Remote Controller Remote Controller 23 ...
Страница 43: ...SiBE28 804 32 Functional Description 6 Outdoor Unit Fan Speed Control 81 6 1 Outdoor Unit Fan Speed Control 81 ...
Страница 93: ...Outdoor Unit Fan Speed Control SiBE28 804 82 Functional Description ...
Страница 131: ...Test Run and Operation Data SiBE28 804 120 Test Operation ...
Страница 251: ...Troubleshooting by Remote Controller Display LED Display SiBE28 804 240 Troubleshooting ...
Страница 277: ...PCB Layout SiBE28 804 266 Appendix ...
Страница 297: ...RZQ100 140C7 RZQS125 140C7V1B SiBE28 804 286 Removal Procedure ...
Страница 311: ...SiBE28 804 iv Index ...