SiBE28-804
Indoor Unit Functional Concept
Functional Description
57
2.5
Draft Avoidance Control 2
Purpose
The purpose of the draft avoidance control 2 is to avoid draft when the flap is moving.
Starting
conditions
The draft avoidance control 2 is activated when:
Hot start is finished, or
Cold air prevention control is finished.
Time chart
If the fan speed is set to "H", the fan turns at low speed for a certain amount of time.
Used input
Draft avoidance control 2 uses the following inputs:
Fan
Flap
Hot start finished
Setting
OFF/LL
L
H
Po0
T
T = 24 s
FCQ: T = 5s
Input
Connection on
indoor PCB
Connection on
outdoor PCB
Limit switch for flaps
33S
—
No. of fan turns
X26A
—
Содержание FHQ100BUV1B x 2
Страница 1: ...SiBE28 804 SkyAir RZQ71C7V1B RZQ100 140C7V1B RZQS71 100C7V1B RZQS125 140C7V1B R 410A Heat Pump 50Hz ...
Страница 13: ...SiBE28 804 2 ...
Страница 19: ...Model Name and Power Supply SiBE28 804 8 General Information ...
Страница 29: ...Specifications SiBE28 804 18 Specifications ...
Страница 33: ...Wired Remote Controller SiBE28 804 22 Remote Controller 1 2 Installation ...
Страница 34: ...SiBE28 804 Wired Remote Controller Remote Controller 23 ...
Страница 43: ...SiBE28 804 32 Functional Description 6 Outdoor Unit Fan Speed Control 81 6 1 Outdoor Unit Fan Speed Control 81 ...
Страница 93: ...Outdoor Unit Fan Speed Control SiBE28 804 82 Functional Description ...
Страница 131: ...Test Run and Operation Data SiBE28 804 120 Test Operation ...
Страница 251: ...Troubleshooting by Remote Controller Display LED Display SiBE28 804 240 Troubleshooting ...
Страница 277: ...PCB Layout SiBE28 804 266 Appendix ...
Страница 297: ...RZQ100 140C7 RZQS125 140C7V1B SiBE28 804 286 Removal Procedure ...
Страница 311: ...SiBE28 804 iv Index ...