SiBE28-804
Troubleshooting Based on Equipment Condition
Troubleshooting
141
2.11 Remote Controller LCD Displays "
88
"
Applicable Model
All models of SkyAir series
Error Detection
Method
Error Generating
Condition
Supposed
Causes
Troubleshooting
Check the unit based on
indoor unit LED and outdoor
unit LED. (Trouble Shooting)
Trouble
generates just after power
supply ON
Is the
position of (SS 1)
on indoor unit PC board at
"Emergency"?
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
The unit is checking to confirm
that remote controller is normal.
Indication appears for short time.
Turn the switch to "Normal", and
reset power supply.
YES
YES
NO
NO
(S1999)
Содержание FHQ100BUV1B x 2
Страница 1: ...SiBE28 804 SkyAir RZQ71C7V1B RZQ100 140C7V1B RZQS71 100C7V1B RZQS125 140C7V1B R 410A Heat Pump 50Hz ...
Страница 13: ...SiBE28 804 2 ...
Страница 19: ...Model Name and Power Supply SiBE28 804 8 General Information ...
Страница 29: ...Specifications SiBE28 804 18 Specifications ...
Страница 33: ...Wired Remote Controller SiBE28 804 22 Remote Controller 1 2 Installation ...
Страница 34: ...SiBE28 804 Wired Remote Controller Remote Controller 23 ...
Страница 43: ...SiBE28 804 32 Functional Description 6 Outdoor Unit Fan Speed Control 81 6 1 Outdoor Unit Fan Speed Control 81 ...
Страница 93: ...Outdoor Unit Fan Speed Control SiBE28 804 82 Functional Description ...
Страница 131: ...Test Run and Operation Data SiBE28 804 120 Test Operation ...
Страница 251: ...Troubleshooting by Remote Controller Display LED Display SiBE28 804 240 Troubleshooting ...
Страница 277: ...PCB Layout SiBE28 804 266 Appendix ...
Страница 297: ...RZQ100 140C7 RZQS125 140C7V1B SiBE28 804 286 Removal Procedure ...
Страница 311: ...SiBE28 804 iv Index ...