2.6
Malfunctioning Capacity Setting (
AJ
)
Error code
AJ
LED indications
The table below shows the LED indications.
Error generation
The error is generated when the following conditions are fulfilled:
Causes
The possible causes are:
Q
Malfunctioning capacity setting adaptor connection
Q
Malfunctioning indoor unit PCB.
Capacity setting
adaptor
The capacity is set in the PCB’s memory IC. A capacity setting adaptor that matches the capacity of
the unit is required in the following case:
In case the indoor PCB installed at the factory is for some reason changed at the installation site, the
capacity will not be contained in the replacement PCB. To set the correct capacity for the PCB you
have to connect a capacity setting adaptor with the correct capacity setting to the PCB. The capacity
setting for the PCB will become the capacity setting of the adaptor because the capacity setting
adaptor has priority.
Operation
HAP (green)
HBP (green)
Normal
c
c
Malfunctioning
c
c
Condition
Description
1
Q
The unit is in operation.
Q
The PCB’s memory IC does not contain the capacity code.
Q
The capacity setting adaptor is not connected.
2
Q
The unit is in operation.
Q
The capacity that is set, does not exist for that unit.
Содержание FCQ35B7V1
Страница 1: ...Service Manual ESIE05 04 R 410A Sky Air Indoor...
Страница 2: ......
Страница 20: ...ESIE05 04 1 2 Part 1 System Outline 3 1 1 5...
Страница 62: ...General Outline ESIE05 04 1 44 Part 1 System Outline 3 1 1 4 5...
Страница 78: ...ESIE05 04 1 60 Part 1 System Outline...
Страница 112: ...Wiring Diagrams ESIE05 04 1 94 Part 1 System Outline 3 1 1 4 5...
Страница 140: ...ESIE05 04 2 2 Part 2 Functional Description 3 1 2 5...
Страница 164: ...ESIE05 04 3 2 Part 3 Troubleshooting 3 1 3 5...
Страница 206: ...Error Codes ESIE05 04 3 44 Part 3 Troubleshooting 3 1 3 4 5...
Страница 224: ...Additional Checks for Troubleshooting ESIE05 04 3 62 Part 3 Troubleshooting 3 1 3 4 5...
Страница 226: ...ESIE05 04 4 2 Part 4 Commissioning and Test Run 3 1 4 5...
Страница 252: ...ESIE05 04 5 2 Part 5 Disassembly and Maintenance 3 1 5...
Страница 384: ...Disassembly and Maintenance ESIE05 04 5 134 Part 5 Disassembly and Maintenance 3 1 5 5...
Страница 390: ...ESIE05 04 vi Index 3 1 4 5 W Wiring diagrams Indoor units k 1 61...