ESIE05-04
Error Codes
Part 3 – Troubleshooting
3–43
4
5
1
3
2.9
Malfunctioning of Moisture Sensor System (
CC
)
Remote
controller
display
CC
Applicable
models
FCQ-D
Method of
malfunction
detection
Even if a malfunction occurs, operation still continues.
Malfunction is detected according to the moisture (output voltage) detected by the moisture
sensor.
Malfunction
decision
conditions
When the moisture sensor is disconnected or short-circuited
Supposed
causes
Q
Faulty sensor
Q
Disconnection
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector, or parts damage may be
occurred.
Is
the
code
"CC"
displayed
on
the
remote
controller?
Turn
the
power
supply
off
once
and
back
on.
Yes
Replace
the
moisture
sensor
PC
board
assembly
(A4P).
Problem
could
be
caused
by
external
factor
(noise,
etc.)
other
than
malfunction.
No
Содержание FCQ35B7V1
Страница 1: ...Service Manual ESIE05 04 R 410A Sky Air Indoor...
Страница 2: ......
Страница 20: ...ESIE05 04 1 2 Part 1 System Outline 3 1 1 5...
Страница 62: ...General Outline ESIE05 04 1 44 Part 1 System Outline 3 1 1 4 5...
Страница 78: ...ESIE05 04 1 60 Part 1 System Outline...
Страница 112: ...Wiring Diagrams ESIE05 04 1 94 Part 1 System Outline 3 1 1 4 5...
Страница 140: ...ESIE05 04 2 2 Part 2 Functional Description 3 1 2 5...
Страница 164: ...ESIE05 04 3 2 Part 3 Troubleshooting 3 1 3 5...
Страница 206: ...Error Codes ESIE05 04 3 44 Part 3 Troubleshooting 3 1 3 4 5...
Страница 224: ...Additional Checks for Troubleshooting ESIE05 04 3 62 Part 3 Troubleshooting 3 1 3 4 5...
Страница 226: ...ESIE05 04 4 2 Part 4 Commissioning and Test Run 3 1 4 5...
Страница 252: ...ESIE05 04 5 2 Part 5 Disassembly and Maintenance 3 1 5...
Страница 384: ...Disassembly and Maintenance ESIE05 04 5 134 Part 5 Disassembly and Maintenance 3 1 5 5...
Страница 390: ...ESIE05 04 vi Index 3 1 4 5 W Wiring diagrams Indoor units k 1 61...