Installation and operation manual
39
EWAQ016~ EWYQ016~064BAW
Packaged air-cooled water chiller
4PW70082-1C – 2013.07
6.1.1.
Field settings table
First
code
Second
code
Setting name
Installer setting at variance with default value
Default
value
Range
Step
Unit
Date
Value
Date
Value
0
Remote control setup
00
User permission level
2
2~3
1
—
01
Room temperature compensation value
0
–5~5
0.5
°C
02
Not applicable. Do not change the default value.
1
—
—
—
03
Status: space heating schedule timer mode
Method 1=1 / Method 2=0
1 (ON)
0/1
—
—
04
Status: space cooling schedule timer mode
Method 1=1 / Method 2=0
1 (ON)
0/1
—
—
1
Settings are not applicable
00
Not applicable. Do not change the default value.
1
—
—
—
01
Not applicable. Do not change the default value.
1:00
—
—
—
02
Not applicable. Do not change the default value.
0
—
—
—
03
Not applicable. Do not change the default value.
15:00
—
—
—
2
Automatic setback function
00
Status: setback operation
1 (ON)
0/1
—
—
01
Setback operation start time
23:00
0:00~23:00
1:00
hour
02
Setback operation stop time
5:00
0:00~23:00
1:00
hour
3
Weather dependent set point
00
Low ambient temperature (Lo_A)
–10
–20~5
1
°C
01
High ambient temperature (Hi_A)
15
10~20
1
°C
02
Set point at low ambient temperature (Lo_Ti)
40
25~80
1
°C
03
Set point at high ambient temperature (Hi_Ti)
25
25~80
1
°C
4
Settings are not applicable
00
Not applicable. Do not change the default value.
1
—
—
—
01
Not applicable. Do not change the default value.
Fri
—
—
—
02
Not applicable. Do not change the default value.
23:00
—
—
—
5
Automatic setback and disinfection set point
00
Not applicable. Do not change the default value.
70
—
—
—
01
Not applicable. Do not change the default value.
10
—
—
—
02
Leaving water setback temperature
5
0~10
1
°C
03
Room setback temperature
18
17~23
1
°C
04
Not applicable. Do not change the default value.
1
—
—
—
6
Option setup
01
Optional room thermostat installed
0
0~2
—
—
03
Negative leaving water temperature setting
0
0~–10
–1
°C
7
Option setup
00
Forced pump operation
1 (ON)
0/1
—
—
8
Option setup
00
Remote controller temperature control
0 (OFF)
0/1
—
—
01
Not applicable. Do not change the default value.
1
—
—
—
03
Not applicable. Do not change the default value.
1
—
—
—
04
Status: freeze-up prevention
0 0~2
1
—
9
Automatic temperature compensation
00
Leaving water temperature compensation value
(heating)
0
–2~2
0.2
°C
01
Leaving water thermistor auto corrective function
1 (ON)
0/1
1
—
02
Not applicable. Do not change the default value.
0
—
—
—
03
Leaving water temperature compensation value
(cooling)
0
–2~2
0.2
°C
04
Not applicable. Do not change the default value.
0
—
—
—