7
|
Unit installation
Installer reference guide
62
ERGA04~08EAV3(A) + EHBH/X04+08EA/EJ6V+9W
Daikin Altherma 3 R W
4P629085-1 – 2020.08
7.2 Opening and closing the units
7.2.1 About opening the units
At certain times, you have to open the unit.
Example:
▪
When connecting the refrigerant piping
▪
When connecting the electrical wiring
▪
When maintaining or servicing the unit
DANGER: RISK OF ELECTROCUTION
Do NOT leave the unit unattended when the service cover is removed.
7.2.2 To open the outdoor unit
DANGER: RISK OF ELECTROCUTION
DANGER: RISK OF BURNING/SCALDING
See
"8.3.8 To connect the refrigerant piping to the outdoor unit"
87] and
"9.2.1 To connect the electrical wiring to the outdoor unit"
7.2.3 To close the outdoor unit
1
Close the switch box cover.
2
Close the service cover.
NOTICE
When closing the outdoor unit cover, make sure that the tightening torque does NOT
exceed 4.1 N•m.
7.2.4 To open the indoor unit
Overview
1
2
3
1
4
4
1
Front panel
2
Switch box cover
3
Switch box
4
User interface panel
Open
1
Remove the front panel.
Содержание ERGA04EAV3A