When
Emergency
is set to
Automatic
and a heat pump failure occurs:
-
the backup heater automatically takes over the heat load,
-
the booster heater in the optional tank automatically takes over the domestic
hot water production.
▪
When
Emergency
is set to
Manual
and a heat pump failure occurs, the
domestic hot water operation and space heating stops.
To manually recover it via the user interface, go to the
Malfunctioning
main
menu screen and confirm whether the backup heater and/or booster heater can
take over the heat load or not.
To keep energy consumption low, we recommend to set
Emergency
to
auto SH
reduced/DHW off
if the house is unattended for longer periods.
#
Code
Description
[9.5.1]
[4-06]
▪
0:
Manual
▪
1:
Automatic
▪
2:
auto SH reduced/DHW on
▪
3:
auto SH reduced/DHW off
▪
4:
auto SH normal/DHW off
INFORMATION
The auto emergency setting can be set in the menu structure of the user interface
only.
INFORMATION
If [4‑03]=1 or 3, then
Emergency
=
Manual
is not applicable for the booster heater.
INFORMATION
If a heat pump failure occurs and
Emergency
is set to
Manual
, the room frost
protection function, the underfloor heating screed dryout function, and the water
pipe antifreeze function will remain active even if the user does NOT confirm
emergency operation.
HP forced off
HP forced off
mode can be activated to allow the backup heater to provide
domestic hot water and space heating. Cooling is NOT possible when this mode is
activated.
#
Code
Description
[9.5.2]
[7-06]
Activation of the
HP forced off
mode:
▪
0:
disabled
▪
1:
enabled
Balancing
Priorities
For systems with a separate domestic hot water tank.