13
|
Maintenance and service
Installer reference guide
223
ERGA04~08EAV3(A) + EHBH/X04+08EA/EJ6V+9W
Daikin Altherma 3 R W
4P629085-1 – 2020.08
a
b
a
Bottom part to be unscrewed
b
Water filter housing
3
Remove the strainer and the rolled‑up filter from the water filter housing and
clean with water.
4
Install the cleaned rolled‑up filter and strainer in the water filter housing.
INFORMATION
Correctly install the strainer in the magnetic filter/dirt separator housing using the
protrusions.
a
b
c
c
a
Rolled‑up filter
b
Strainer
c
Protrusion
5
Install and properly tighten the bottom of the water filter housing.
13.5.3 To install the water filter
CAUTION
Check the condition of the O-rings and replace if needed. Apply water to the O-rings
before installation.
1
Install the water filter in the correct location.