Installer reference guide
61
08 + ERLQ004~008
Daikin Altherma - Low Temperature Split
4P313774-1 – 2012.05
8 Configuration
Power saving function
Defines whether the outdoor unit power supply can be interrupted
(internally by indoor unit control) during stand-still conditions (no
space heating/cooling nor domestic hot water demand). The final
decision to allow power interruption of the outdoor unit during
standstill depends on the ambient temperature, compressor
conditions and minimum internal timers.
To enable the power saving function setting, [E-08] needs to be
enable at the user interface in combination with the removal of the
power saving connector at the outdoor unit. The power saving
connector at the outdoor unit shall only be removed when the main
power supply to the application is switched OFF.
Power consumption control
Only applicable for EHBH/X04+08 + EHVH/X04+08. See
"5 Application guidelines" on page 9 for detailed information about
this functionality.
Pwr consumpt. control
Note: power consumption control only based on heater priority is
possible for EHBH/X04+08 and EHVH/X04+08 models, but also for
EHBH/X16CA and EHVH/X16 models. Hereto you can limit the
operation of both electrical heaters (backup heater and booster
heater) by the following setting.
INFORMATION
Only applicable for ERLQ004~008CAV3.
#
Code
Description
N/A
[E-08]
Power saving function for outdoor unit:
Q
0 (default): Disabled
Q
1: Enabled
#
Code
Description
[A.6.3.1]
[4-08]
Mode:
Q
0 (No limitation)(default): Disabled.
Q
1 (Continuous): Enabled: You can
set one power limitation value (in A
or kW) to which the system power
consumption will be limited for all
the time.
Q
2 (Digital inputs): Enabled: You
can set up to four different power
limitation values (in A or kW) to
which the system power
consumption will be limited when
the corresponding digital input
asks.
3x
1 2 3
[A.6.3.2]
[4-09]
Type:
Q
0 (Current): The limitation values
are set in A.
Q
1 (Power)(default): The limitation
values are set in kW.
[A.6.3.3]
N/A
Value: Only applicable in case of full
time power limitation mode.
0~50 A, step 1 A (default: 50 A)
[A.6.3.4]
N/A
Value: Only applicable in case of full
time power limitation mode.
0~20 kW, step 0.5 kW (default: 20 kW)
Amp. limits for DI: Only applicable in case of power limitation mode
based on digital inputs and based on current values.
[A.6.3.5.1]
[5-05]
Limit DI1
0~50 A, step 1 A (default: 50 A)
[A.6.3.5.2]
[5-06]
Limit DI2
0~50 A, step 1 A (default: 50 A)
[A.6.3.5.3]
[5-07]
Limit DI3
0~50 A, step 1 A (default: 50 A)
[A.6.3.5.4]
[5-08]
Limit DI4
0~50 A, step 1 A (default: 50 A)
kW limits for DI: Only applicable in case of power limitation mode
based on digital inputs and based on power values.
[A.6.3.6.1]
[5-09]
Limit DI1
0~20 kW, step 0.5 kW (default: 20 kW)
[A.6.3.6.2]
[5-0A]
Limit DI2
0~20 kW, step 0.5 kW (default: 20 kW)
[A.6.3.6.3]
[5-0B]
Limit DI3
0~20 kW, step 0.5 kW (default: 20 kW)
[A.6.3.6.4]
[5-0C]
Limit DI4
0~20 kW, step 0.5 kW (default: 20 kW)
Priority: Only applicable in case of an optional EKHW*.
[A.6.3.7]
[4-01]
Q
0 (None)(default): No heater is
prioritized. If the power
consumption control is enabled,
the booster heater will be limited
first.
Q
1 (BSH): The booster heater is
prioritized. If the power
consumption control is enabled,
the backup heater (step 1 and/or
step 2) will be limited first, before
the booster heater is limited.
Q
2 (BUH): The backup heater is
prioritized. If the power
consumption control is enabled,
the booster heater will be limited
first, before the backup heater is
limited.
#
Code
Description
Содержание EHBH04CA
Страница 106: ...4P313774 1 2012 05 Copyright 2012 Daikin ...