08 + ERLQ004~008
Daikin Altherma - Low Temperature Split
4P313774-1 – 2012.05
Installer reference guide
16
5 Application guidelines
Determining the volume and desired temperature for the DHW
tank
5.4.4 Setup and configuration – DHW tank
Q
For large DHW consumptions, you can heat up the DHW tank
several times during the day.
Q
To heat up the DHW tank to the desired DHW tank temperature,
you can use the following energy sources:
Q
Thermodynamic cycle of the heat pump
Q
Electrical backup heater (for integrated DHW tank)
Q
Electrical booster heater (for standalone DHW tank)
Q
Solar panels
Q
For more information about:
Q
Optimizing the energy consumption for producing domestic
hot water, see the configuration chapter.
Q
Connecting the electrical wiring of the standalone DHW
tank to the indoor unit, see the installation chapter.
Q
Connecting the water piping of the standalone DHW tank to
the indoor unit, see the installation manual of the DHW
tank.
5.4.5 Combination: Standalone DHW tank + Solar
panels
By connecting the DHW tank to solar panels, the DHW tank can be
heated by solar energy.
For installation instructions, see the installation manual of the solar kit
and addendum book for optional equipment.
5.4.6 DHW pump for instant hot water
Setup
Q
By connecting a DHW pump, instant hot water can be available
at the tap.
Q
The DHW pump and the installation are field supply and the
responsibility of the installer.
Q
For more information about connecting the recirculation
connection (for integrated DHW tank), see the installation
chapter.
Configuration
Q
For more information, see the configuration chapter.
Q
You can program a schedule to control the DHW pump via the
user interface. For more information, see the user reference
guide.
Formula
Example
V
1
= V
2
+ V
2
x (T
2
- 40) / (40 - T
1
)
If:
Q
V
2
= 180 l
Q
T
2
= 54°C
Q
T
1
= 15°C
Then V
1
= 280 l
V
2
= V
1
x (40 - T
1
) / (T
2
- T
1
)
If:
Q
V
1
= 480 l
Q
T
2
= 54°C
Q
T
1
= 15°C
Then V
2
= 307 l
V
1
:
DHW consumption (equivalent hot water volume at 40°C)
V
2
:
Required DHW tank volume if only heated once
T
2
:
DHW tank temperature
T
1
:
Cold water temperature
a
Solar panels
b
Solar pump station
c
Solar pump station controller with temperature sensors
c1
Tank temperature sensor
c2
Return temperature sensor to solar panels
c3
Supply temperature with flow meter from solar panels
c4
Solar panel temperature sensor
d
Solar kit
e
DHW temperature sensor of the unit
f
Solenoid 2-way valve (only for UK). Obligatory for
compliance to UK building regulation G3.
Heating system
Example of unit
a
Indoor unit
b
DHW tank
c
DHW pump
f
Shower
g
Cold water
h
Domestic hot water OUT
i
Recirculation connection
M
a
c
d
b
c.1
c.2
c.3
e
c.4
f
≥0.5 m
c
f
a
b
g
h
i