7 Installation
7.6.5 To connect the backup heater power supply
The backup heater capacity can vary, depending on the indoor unit
model. Make sure that the power supply is in accordance with the
backup heater capacity, as listed in the table below.
1
Connect the backup heater power supply.
For *3V models, use a single pole fuse for F1B. For *9W models,
use a double pole fuse for F1B.
Special remark for fuses:
CAUTION
If the indoor unit has a tank with a built-in electrical booster
heater (EKHW*), use a dedicated power circuit for the
backup heater and booster heater. NEVER use a power
circuit shared by another appliance. This power circuit must
be protected with the required safety devices according to
the applicable legislation.
Backup
heater type
Backup
heater
capacity
Power
supply
Maximum
running
current
Z
max
(
Ω
)
*3V
3 kW
1~ 230 V
13 A
—
*9W
3 kW
1~ 230 V
13 A
—
6 kW
1~ 230 V
26 A
(a)(b)
0.29
6 kW
3~ 230 V
15 A
(b)
—
6 kW
3N~ 400 V
8.6 A
—
9 kW
3N~ 400 V
13 A
—
(a)
Equipment complying with EN/IEC 61000-3-12
(European/International Technical Standard setting the limits for
harmonic currents produced by equipment connected to public low-
voltage systems with input current >16 A and
≤
75 A per phase.).
(b)
This equipment complies with EN/IEC 61000-3-11
(European/International Technical Standard setting the limits for
voltage changes, voltage fluctuations and flicker in public low-
voltage supply systems for equipment with rated current
≤
75 A)
provided that the system impedance Z
sys
is less than or equal to
Z
max
at the interface point between the user's supply and the public
system. It is the responsibility of the installer or user of the
equipment to ensure, by consultation with the distribution network
operator if necessary, that the equipment is connected only to a
supply with a system impedance Z
sys
less than or equal to Z
max
.
Backup heater
type
(a)
Connections to
backup heater power
supply
Connections to
terminals
3 kW 1~ 230 V
(*3V)
—
3 kW 1~ 230 V
(*9W)
6 kW 1~ 230 V
(*9W)
6 kW 3~ 230 V
(*9W)
6 kW 3N~ 400 V
(*9W)
9 kW 3N~ 400 V
(*9W)
(a)
For configuration of the backup heater, see Quick wizard: Standard.
F1B
L N
L N
F1B
L
N
L
N
1 2 3 4
6 7 8
5
X6M
X7M
1 2 3 4
6 7 8
5
X6M
X7M
F1B
L1
L1 L2
L2 L3
L3
L1 L2 L3
1 2 3 4
6 7 8
5
X6M
X7M
F1B
L1
L1 L2
L2 L3
L3
L1 L2 L3
1 2 3 4
6 7 8
5
X6M
X7M
Содержание EHBH04CA
Страница 106: ...4P313774 1 2012 05 Copyright 2012 Daikin ...