Installer reference guide
9
08 + ERLQ004~008
Daikin Altherma - Low Temperature Split
4P313774-1 – 2012.05
5 Application guidelines
5
Application guidelines
5.1
Overview: Application guidelines
The purpose of the application guidelines is to give a glance of the
possibilities of the Daikin heat pump system.
This chapter contains applications guidelines for:
Q
Setting up the space heating/cooling system
Q
Setting up an auxiliary heat source for space heating
Q
Setting up the domestic hot water tank
Q
Setting up the energy metering
Q
Setting up the power consumption
Q
Setting up an external temperature sensor
5.2
Setting up the space heating/cooling system
The Daikin heat pump system supplies leaving water to heat emitters
in one or more rooms.
Because the system offers a wide flexibility to control the temperature
in each room, you need to answer the following questions first:
Q
How many rooms are heated (or cooled) by the Daikin
heat pump system?
Q
Which heat emitter types are used in each room and what is
their design leaving water temperature?
Once the space heating/cooling requirements are clear, Daikin
recommends to follow the setup guidelines below.
5.2.1 Single room
Under floor heating or radiators – Wired room
thermostat
Setup
Q
The under floor heating or radiators are directly connected to the
indoor unit.
Q
The room temperature is controlled by the user interface, which
is used as room thermostat. Possible installations:
Q
User interface (standard equipment) installed in the room
and used as room thermostat
Q
User interface (standard equipment) installed at the indoor
unit and used for control close to the indoor unit + user
interface (optional equipment EKRUCAL) installed in the
room and used as room thermostat
Configuration
Benefits
Q
Cost effective
.
You do NOT need an additional external room
thermostat.
Q
Highest comfort and efficiency
. The smart room thermostat
functionality can decrease or increase the desired leaving water
temperature based on the actual room temperature
(modulation). This results in:
Q
Stable room temperature matching the desired temperature
(higher comfort)
Q
Less ON/OFF cycles (more quiet, higher comfort and
higher efficiency)
Q
Lowest possible leaving water temperature (higher
efficiency)
Q
Easy
. You can easily set the desired room temperature via the
user interface:
Q
For your daily needs, you can use preset values and
schedules.
Q
To deviate from your daily needs, you can temporarily
overrule the preset values and schedules, use the holiday
mode…
Under floor heating or radiators – Wireless room
thermostat
Setup
Q
The under floor heating or radiators are directly connected to the
indoor unit.
Q
The room temperature is controlled by the wireless external
room thermostat (optional equipment EKRTR1).
NOTICE
Q
The illustrations in the application guidelines are
meant for reference only, and are NOT to be used as
detailed hydraulic diagrams. The detailed hydraulic
dimensioning and balancing are NOT shown, and are
the responsibility of the installer.
Q
For more information about the configuration settings
to optimize heat pump operation, see the configuration
chapter.
A
Main leaving water temperature zone
B
One single room
a
User interface used as room thermostat
B
A
a
Setting
Value
Unit temperature control:
Q
#: [A.2.1.7]
Q
Code: [C-07]
2 (RT control): Unit operation is
decided based on the ambient
temperature of the user interface.
Number of water temperature
zones:
Q
#: [A.2.1.8]
Q
Code: [7-02]
0 (1 LWT zone): Main
A
Main leaving water temperature zone
B
One single room
a
Receiver for wireless external room thermostat
b
Wireless external room thermostat
B
A
b
a