8/11
Breadcrumb Field code
Setting name
Range, step
Default value
Date
Value
Field settings table
Installer setting at variance with
default value
9.I
[4-02]
R/W
14~35°C, step: 1°C
with BUH:
35°C
without BUH:
25°C
9.I
[4-03]
R/W
0: Restricted
1: Allowed
2: Overlap
3: Compressor off
4: Legionella only
9.I
[4-04]
0: Intermittent (not to be used)
1: Continuous
2: Off
9.I
[4-05]
0
9.I
[4-06]
R/W
0: Manual
1: Automatic(normal SH/DHW ON)
2: Auto red SH/DHW ON
3: Auto red SH/DHW OFF
4: SH ON/DHW OFF
9.I
[4-07]
6
9.I
[4-08]
R/W
0: No limitation
1: Continuous
2: Digital inputs
9.I
[4-09]
R/W
0: Current
1: Power
9.I
[4-0A]
R/W
0: 1
1: 1/1+2
2: 1/2
3: 1/2 + 1/1+2 in emergency
9.I
[4-0B]
R/W
1~10°C, step: 0,5°C
1°C
9.I
[4-0D]
R/W
1~10°C, step: 0,5°C
3°C
9.I
[4-0E]
6
9.I
[5-00]
R/W
0: No
1: Yes
9.I
[5-01]
R/W
-15~35°C, step: 1°C
0°C
9.I
[5-02]
R/W
0: Disabled
1: Enabled
9.I
[5-03]
R/W
-15~35°C, step: 1°C
0°C
9.I
[5-04]
R/W
0~20°C, step: 1°C
10°C
9.I
[5-05]
R/W
0~50 A, step: 1 A
50 A
9.I
[5-06]
R/W
0~50 A, step: 1 A
50 A
9.I
[5-07]
R/W
0~50 A, step: 1 A
50 A
9.I
[5-08]
R/W
0~50 A, step: 1 A
50 A
9.I
[5-09]
R/W
0~20 kW, step: 0,5 kW
20 kW
9.I
[5-0A]
R/W
0~20 kW, step: 0,5 kW
20 kW
9.I
[5-0B]
R/W
0~20 kW, step: 0,5 kW
20 kW
9.I
[5-0C]
R/W
0~20 kW, step: 0,5 kW
20 kW
9.I
[5-0D]
R/W (*1)
R/O (*2)
0: 230V, 1~
1: 230V, 3~
2: 400V, 3~
9.I
[5-0E]
1
9.I
[6-00]
R/W
2~40°C, step: 1°C
27°C
9.I
[6-01]
R/W
0~10°C, step: 1°C
2°C
9.I
[6-02]
R/W
0~10kW, step: 0,2kW
3kW
9.I
[6-03]
R/W
0~10kW, step: 0,2kW
0kW (*1)
3kW (*2)
9.I
[6-04]
R/O (*2)
R/W (*1)
0~10kW, step: 0,2kW
0kW
9.I
[6-05]
0
9.I
[6-06]
0
9.I
[6-07]
R/W
0~200W, step: 10W
0W
9.I
[6-08]
R/W
2~20°C, step: 1°C
10°C
9.I
[6-09]
0
9.I
[6-0A]
R/W
30~[6-0E]°C, step: 1°C
50°C
9.I
[6-0B]
R/W
30~min(50, [6-0E])°C, step: 1°C
45°C
9.I
[6-0C]
R/W
30~min(50, [6-0E])°C, step: 1°C
45°C
9.I
[6-0D]
R/W
0: Reheat only
1: sched.
2: Scheduled only
9.I
[6-0E]
R/W
40~75°C, step: 1°C
60°C
[E-07]=0
40~80°C, step: 1°C
60°C
[E-07]=5
9.I
[7-00]
R/W
0~4°C, step: 1°C
0°C
9.I
[7-01]
R/W
2~40°C, step: 1°C
2°C
9.I
[7-02]
R/W
0: 1 LWT zone
1: 2 LWT zones
9.I
[7-03]
2.5
9.I
[7-04]
0
--
--
What is the desired reheat temperature?
What is the desired DHW production type?
What is the maximum
DHW
temperature setpoint?
Domestic hot water booster heater overshoot temperature.
Domestic hot water booster heater hysteresis.
How many leaving water temperature zones are there?
--
What is the capacity of the bottom plate heater?
What is the hysteresis to be used in reheat mode?
--
What is the desired comfort storage temperature?
What is the desired eco storage temperature?
The temperature difference determining the heat pump ON temperature.
The temperature difference determining the heat pump OFF temperature.
What is the capacity of the booster heater?
What is the capacity of the backup heater step 1?
What is the capacity of the backup heater step 2?
--
What is the requested limit for DI1?
What is the requested limit for DI2?
What is the requested limit for DI3?
What is the requested limit for DI4?
Backup heater voltage
--
Space heating priority temperature.
Set point correction for domestic hot water temperature.
What is the requested limit for DI1?
What is the requested limit for DI2?
What is the requested limit for DI3?
What is the requested limit for DI4?
Automatic cooling/heating changeover hysteresis.
Automatic cooling/heating changeover offset.
--
Equilibrium: Deactivate backup heater (or external backup heat source in case of a
bivalent system) above the equilibrium temperature for space heating?
What is the equilibrium temperature for the building?
Space heating priority.
--
Emergency
--
Which power limitation mode is required on the system?
Which power limitation type is required?
Backup heater configuration
Below which outdoor temperature is heating allowed?
Operation permission of the booster heater.
Water pipe freeze prevention