11
|
Configuration
Installer reference guide
155
EBLA09~16D + EDLA09~16D
Daikin Altherma 3 M
4P620241-1B – 2022.05
#
Code
Description
[2.1]
N/A
Schedule
:
▪
0:
No
▪
1:
Yes
Heating schedule
Define a heating temperature schedule for the main zone via [2.2]
Heating
schedule
.
See
"11.4.3 Schedule screen: Example"
Cooling schedule
Define a cooling temperature schedule for the main zone via [2.3]
Cooling
schedule
.
See
"11.4.3 Schedule screen: Example"
Setpoint mode
Define the setpoint mode:
▪
Fixed
: the desired leaving water temperature does not depend on the outdoor
ambient temperature.
▪
In
WD heating, fixed cooling
mode, the desired leaving water
temperature:
-
depends on the outdoor ambient temperature for heating
-
does NOT depend on the outdoor ambient temperature for cooling
▪
In
Weather dependent
mode, the desired leaving water temperature depends
on the outdoor ambient temperature.
#
Code
Description
[2.4]
N/A
Setpoint mode
:
▪
Fixed
▪
WD heating, fixed cooling
▪
Weather dependent
When weather dependent operation is active, low outdoor temperatures will result
in warmer water and vice versa. During weather dependent operation, the user
can shift the water temperature up or down by a maximum of 10°C.
Heating WD curve
Set weather-dependent heating for the main zone (if [2.4]=1 or 2):
Содержание EBLA09D V3 Series
Страница 279: ...11 11...
Страница 280: ...4P620241 1B 2022 05 Copyright 2020 Daikin Verantwortung f r Energie und Umwelt...