NOTICE
If
Emergency
is set to
Manual
([9.5.1]=0), and the unit is triggered to start
emergency operation, the unit will stop and needs to be recovered manually via the
user interface. To recover operation manually, go to the
Malfunctioning
main
menu screen, and confirm emergency operation before starting.
Room frost protection is active even if the user does not confirm emergency
operation.
Setpoint range
Only applicable in room thermostat control.
To save energy by preventing overheating or undercooling the room, you can limit
the range of the room temperature for heating and/or cooling.
NOTICE
When adjusting the room temperature ranges, all desired room temperatures are
also adjusted to guarantee they are between the limits.
#
Code
Description
[1.5.1]
[3-07]
Heating minimum
[1.5.2]
[3-06]
Heating maximum
[1.5.3]
[3-09]
Cooling minimum
[1.5.4]
[3-08]
Cooling maximum
Room sensor offset
Only applicable in room thermostat control.
To calibrate the (external) room temperature sensor, give an offset to the value of
the room thermistor as measured by the Human Comfort Interface (BRC1HHDA
used as room thermostat) or by the external room sensor. The setting can be used
to compensate for situations where the Human Comfort Interface or the external
room sensor cannot be installed at the ideal location.
See
"6.7 Setting up an external temperature sensor"
#
Code
Description
[1.6]
[2-0A]
Room sensor offset
(Human Comfort
Interface (BRC1HHDA used as room thermostat)):
Offset on the actual room temperature measured
by the Human Comfort Interface.
▪
–5°C~5°C, step 0.5°C
[1.7]
[2-09]
Room sensor offset
(external room sensor
option): Only applicable if the external room
sensor option is installed and configured.
▪
–5°C~5°C, step 0.5°C
Room comfort setpoint
Restriction:
Only applicable if:
▪
Smart Grid is enabled ([9.8.4]=
Smart grid
), and
▪
Room buffering is enabled ([9.8.7]=
Yes
)