9.8.3.
Detecting all connected equipment ([2] Address Check)
Before commissioning, it is necessary to check if all connected
(Daikin) devices have a correct DIII-NET and AirNet address. The
address check will detect faulty address settings (missing addresses
or duplicate addresses).
To detect all connected (Daikin) devices, proceed as follows:
1
In the net commissioning tool, click
Address Check
.
2
In the
Check Address
window, click
Start Check
.
3
Wait until all VRV outdoor and VRV indoor units are listed.
It might take several minutes until all units are listed.
4
The check will continue to search, even if all units have been
found. If you see that all units are listed, stop the check
completely by clicking
Exit Check
.
5
If the check has been completed, click
Close
.
9.8.4.
Configuring all connected devices ([3] Port Setup)
To configure or correct the information of the detected devices (model
name, serial number, etc), proceed as follows:
1
In the net commissioning tool, click
Port Setup
.
The
DIII Lines List
window will be displayed, with all the DIII-
NET addresses where one or more device(s) are connected to.
2
Select the desired DIII-NET port.
3
Click
Outdoor Units.
The
Outdoor Unit Setup
window for this DIII-NET address will
be displayed.
4
Enter the following data for this address
(if applicable / available):
5
Click the upper
Apply
button to confirm these changes.
6
Select the desired outdoor unit from the list of outdoor units.
INFORMATION
If you want to make changes to the configuration of
your outdoor or indoor units, you can pause the check
by clicking
Abort Check
. You can click
Check
Resume
to continue the check.
In the resulting list, all units with correct addresses will
have the
OK
status in the
Result
column. All units
with faulty addresses will have
NG
in the
Result
column. Note that the AirNet addresses of indoor and
outdoor units can be configured in the
Service
Settings
window of the connected wired remote
controller.
Some units may be displayed with
Unknown
model
names. If this occurs, you can appoint the model
name in
"9.8.4. Configuring all connected devices ([3]
.
Field
Explanation
Line Name
Enter the name of the zone, covered by this
unit.
Installation Date
Date of installation of this unit in yyyy/m/d
format.
Piping Length
Refrigerant Charge
Amount
Additional Refrigerant
Charge Amount
If this information is available to you, enter
this in these fields.
This information is not used for monitoring,
but will be included in reports.