44
Model
Tap
Low
Stage
Cool
High
Stage
Cool
Low
Stage
Heat
High
Stage
Heat
A
398
599
667
953
B
557
817
740
1059
C
696
1007
808
1158
D
810
1212
881
1260
A
403
629
855
1202
B
540
806
923
1316
C
705
1023
1033
1389
D
819
1230
1063
1396
A
513
789
867
1228
B
660
967
939
1337
C
791
1182
1016
1430
D
913
1375
1077
1516
A
564
820
1256
1818
B
784
1133
1292
1870
C
982
1464
1316
1910
D
1259
1736
1358
1957
A
547
867
1329
1891
B
831
1160
1362
1940
C
1020
1467
1390
1968
D
1278
1910
1440
2028
A
433
656
687
938
B
541
790
751
950
C
686
972
814
986
D
806
1195
874
992
A
405
624
758
1057
B
549
808
815
1146
C
678
994
882
1256
D
784
1177
946
1349
A
556
837
889
1234
B
714
1022
944
1325
C
838
1206
1019
1442
D
991
1475
1068
1528
A
524
784
1209
1759
B
744
1078
1249
1797
C
927
1388
1277
1840
D
1185
1766
1300
1881
DM97MC0603BN**
DM97MC0803BN**
DM97MC0804CN**
DM97MC1005CN**
DM97MC1205DN**
DC97MC0603BN**
DC97MC0803BN**
DC97MC0804CN**
DC97MC1005CN**
*100% CFM shown. CFM will vary proportionally with the gas valve BTU/H input
.
4. Continuous fan speed is selectable at 25%, 50%, 75%
or 100% of the furnace’s maximum airflow capability.
Example:
If the furnace’s maximum airflow capability
is 2000 CFM, the continuous fan speed at
25% will be 0.25 x 2000 or 500 CFM.
5. Locate the blower speed selection DIP switches on the
integrated control module. Select the desired “cooling”
speed tap by positioning switches 1 and 2 appropriately.
Select the desired “adjust” tap by positioning switches
9 and 10 appropriately. Refer to the DIP switch chart
for switch positions and their corresponding taps. Verify
CFM by noting the number displayed on the dual 7-
segment LED display.
6. The multi-speed circulator blower also offers several
custom ON/OFF ramping profiles for cooling. These
profiles may be used to enhance cooling performance
and increase comfort level. The ramping profiles
are selected using DIP switches 7 and 8. Refer to the
bullet points below for a description of each ramping
profile. Verify CFM by noting the number displayed on
the dual 7-segment LED display.
•
Profile A
provides only an OFF delay of one (1) minute
at 100% of the cooling demand airflow.
OFF
100% CFM
100% CFM
1 min
OFF
Figure 53A
•
Profile B
ramps up to full cooling demand airflow by
first stepping up to 50% of the full demand for 30
seconds. The motor then ramps to 100% of the required
airflow. A one (1) minute OFF delay at 100% of the
cooling airflow is provided.
50% CFM
1/2 min
100% CFM
100% CFM
1 min
OFF
OFF
Figure 53B
•
Profile C
ramps up to 85% of the full cooling demand
airflow and operates there for approximately 7 1/2
minutes. The otor then steps up to the full demand
airflow. Profile C also has a one (1) minute 100% OFF
delay.
100% CFM
OFF
OFF
Figure 53C
•
Profile D
ramps up to 50% of the demand for 1/2 minute,
then ramps to 85% of the full cooling demand airflow
and operates there for approximately 7 1/2 minutes.
The motor then steps up to the full demand airflow.
Profile D has a 1/2 minute at 50% airflow OFF delay.
OFF
OFF
Figure 53D
Airflow Tables
7. Select the heating speed for your model from the heating
speed table in this manual. The “adjust” setting
(already established by the cooling speed selection)
determines which set of speeds are available. The
selected speed must provide a temperature rise within
the rise range listed with the particular model.